AT&T 76450 User Manual

Page 7

Advertising
background image

Common Systems Connection Standards AT&T Services, Inc
Date: June 2013

ATT-TP-76450, Issue 15

Copyright

©

2013, AT&T . All Rights Reserved.

Page 7

2.3.2

Front Power Terminations.


Equipment designed as “front access only” (no rear access allowed) shall have the power
terminations on the front of the equipment. All power leads entering the front or side shall be
protected from accidental bumps, pulls and hits. All power connections shall be clearly labeled.
DC power terminations shall be fully protected with a non-metallic, non-flammable cover.

2.4

DC Connectors


Connectors used to attach the product to external power cabling shall conform to the following
requirements:

2.4.1

8 AWG and Larger Stranded Power Cable


Power input cable that will accept # 8 AWG or larger connector terminations shall use dual
threaded post (stud) termination able to accept the appropriate two-hole crimp connection.
The two post termination may be either 1’,3/4”, 5/8” or 1/2“ on centers. Refer to Table 2-1 for
acceptable connectors.

2.4.2

16 AWG to 10 AWG Stranded Power Cable


For applications where the size of wire supplying or distributing power to/from the equipment is
16 AWG to 10 AWG stranded power cable, pressure crimped ring type connectors shall be
used on the power cable. Refer to Table 2-1 for acceptable connectors.

2.4.3

Equipment surface terminations shall accept crimp connections that meet the
following specifications for 16 AWG and larger stranded power cable:

o

UL486A Wire Connectors and Soldering Lugs for Use with Copper

o

UL467 Grounding and Bonding Equipment Conductors

o

UL 486C Splicing Wire Connectors

o

SAE-AS25036 (Insulated Copper Ring Crimped Terminal - Dimensions)

o

SAE-AS7928 (Copper Ring Crimped Terminal - Specifications)


Equipment submitted for approval should provide a UL listed (power) termination strip designed
and designated as “field wireable” to insure product compliance with the UL listing of the
product. This termination or barrier strip should be able to accommodate a ring lug connectors
that comply with the UL, CSA and Mil Spec listings.

2.4.4

18 AWG Power Cable and Smaller


For applications where the size of wire supplying power to the equipment is 18 AWG power
cable or smaller, mechanical connectors may be used. Refer to Table 2-1 for acceptable
connectors.

Advertising