AT&T 76450 User Manual

Page 19

Advertising
background image

Common Systems Connection Standards AT&T Services, Inc
Date: June 2013

ATT-TP-76450, Issue 15

Copyright

©

2013, AT&T . All Rights Reserved.

Page 19

5.9 Space Between Door/Panel and Fiber Connector


To avoid pinching or reduction of minimum fiber bend radius the minimum distance between
the fiber connector and any door/panel cover shall be a minimum of 3.75 inches.
See Figure 5-1

5.10 Standard Fiber Connector


The AT&T standard fiber connector shall be SC-UPC single mode or LC-UPC single mode type
connector. Application of connector type shall be determined by equip design or manufacturer.

5.11 Alternative FTTP Fiber Connector


The AT&T alternative fiber connector for FTTP shall be SC-APC, SingleMode, 8-degree, keyed
type connector.

5.12 Fiber Transmission Material


Fiber transmission material shall be glass, not plastic or any other material not specifically pre-
approved by AT&T NP&E Staff.

5.13 Maximum optical power levels


Optical aggregate power level must not exceed +16.8 dBm optical power level at any connector
(Hazard Level 3b). If the product exceeds this, there must be an embedded (to the network
equipment) solution to protect the human exposure for both TXMT and RCV including the
Automatic Power Reduction (APR) potential solutions.

Advertising