Operating and installation instructions

Thrust actuator ARI-PREMIO

5.5.14.3 Electronic position indicator (RI32) and position controller (ES11)

together in the actuator

The electronic position indicator RI32 and the electronic position controller ES11 can be
build-in together in the ARI-PREMIO (Except: 5 kN 24V 1,0/1,2 mm/s).
It must be used a double potentiometer with 1000/1000 Ohm.
To install the RI32 and ES11 proceed as follows:
- Switch-off mains voltage and safeguard to prevent it from being switched back on again

accidentally.

- Loosen collar nut / countersunk screw on hood, carefully remove hood.
- Mount RI32 and ES11 with mounting kit according to Fig. 28.

Fig. 28: Installing RI32 / ES11 at the same time as ARI-PREMIO 2.2 – 5 kN

Pos.

Designation

Pos.

Designation

50.67

Potentiometer

50.82

Head cap screw
DIN EN ISO 4762 - M4x12

50.78

Option ES11 or RI21

50.121

Option RI32

Advertising