VENTILATION REQUIREMENTS

A steam ventilation hood is mandatory for the

operation of the oven. The ventilation hood must

be installed in accordance with local building

codes for the steam exhaust and must protrude

12-inches to 20-inches (300 to 500mm) over the

front side of the oven. A grease filter must be

located in the protruding area of the hood.

Grease filters should be thoroughly cleaned on a

regular basis following manufacturer's

instruction. Ventilation hoods must ensure an

adequate amount of incoming air during

operation and must be operated whenever the

combination oven/steamer is used in order to

avoid the accumulation of condensation in the

hood area. See the section titled Gas Exhaust.

POSITIONING ON SITE

Lift the oven from the pallet with a fork lift or

pallet lift truck positioned at the front of the oven.

For damage protection, the use of two wooden

boards, placed between the bottom of the oven

and the lifting forks, is strongly recommended.

To avoid damage, position the lift forks to the left

of the condenser and right of the right leg as

indicated in the diagram at right.

Stand the oven in a level position. Use the

adjustable feet to overcome an uneven floor and

ensure that the unit is level.

It is strongly recommended that table top models

be mounted on a factory supplied stand or a stand

that is stable, open, level, and non-combustible.

Recommended height is 23-inches (584mm).

Adjust the height of floor models for smooth

access of the trolley or cart. When positioning the

oven, observe the minimum space allocation

requirements shown.

To insure proper operation, the installation of this

oven must be completed by qualified technicians

in accordance with the instructions provided in

this manual. Failure to follow the instructions

provided may result in damage to the oven,

building, or cause personal injury to personnel.

L O C AT I O N S I T E & I N S TA L L AT I O N R E Q U I R E M E N T S

NOTE:

To avoid equipment damage, observe
attention label on oven for area to avoid
with lifting fork.

MINIMUM CLEARANCE REQUIREMENTS

L E F T S I D E

6" (152mm)

MINIMUM

18" (457mm)

SERVICE ACCESS RECOMMENDED

20" (508mm)

FROM HEAT PRODUCING EQUIPMENT

R I G H T S I D E

4" (102mm)

B A C K

4" (102mm)

T O P

20" (508mm)

FOR AIR MOVEMENT

B O T T O M

20" (508mm)

FOR AIR MOVEMENT

NOTE:

Additional clearance is needed for service

access. A minimum distance of 18-inches is
strongly recommended. If adequate service
clearance is not provided, it will be necessary to
disconnect the gas, water, and drain to move the
oven with a fork lift for service access. Charges
in connection with inadequate service access is
not covered under warranty.

C A U T I O N

TO PREVENT PERSONAL INJURY,

USE CAUTION WHEN MOVING OR

LEVELING THIS APPLIANCE.