I N S T A L L A T I O N M A N U A L

#MN-28898

PG

. 13

®

C O M B I T HE R M

V E N T I L AT I O N & I N S TA L L AT I O N R E Q U I R E M E N T S

1.

A single gas Combitherm oven requires a

minimum of

28 CFM

make-up air for natural and

propane gas. Kitchen ventilation must include a

provision for an adequate flow of fresh air for

gas combustion and to prevent a negative-

pressure condition. The bottom of the oven

provides air supply access for gas combustion

and must be kept clear at all times.
DO NOT

obstruct or restrict ventilation nor the

air flow required to support combustion.

2. DO NOT

obstruct the flow of the exhaust flue at

the top rear of the oven. It is especially critical

that gas supply piping and electrical support

cord and/or receptacle be routed away from the

path of the hot combustion fumes.

3.

Make certain the oven installation maintains

adequate air ventilation to provide cooling for

electrical and gas components. The area around

the oven should be clear of any obstructions

which might retard the flow of cooling air.

Failure to observe this caution may result in

damage to the components and will void the

warranty.

4.

This oven cannot be direct vented.

5.

Install the oven under a ventilation hood meeting

all applicable code requirements. Combustion

fumes must be vented in accordance with local,

state, or national codes.

Ventilating hoods and exhaust systems shall be

permitted to be used to vent appliances installed in

commercial applications.

Where automatically operated appliances are vented

through a ventilating hood or exhaust system equipped

with a damper or with a power means of exhaust,

provisions shall be made to allow the flow of gas to the

main burners only when the damper is open to a position

to properly vent the appliance and when the power means

of exhaust is in operation.

IN ACCORDANCE WITH

NFPA 54

COMMONWEALTH OF MASSACHUSETTS ONLY

.

An adequate ventilation system is required for

commercial cooking equipment. Information may be

obtained by writing to the National Fire Protection

Association, Batterymarch Park, Quincy, MA 02269.

When writing refer to NFPA No. 96.

D A N G E R

Installation, air adjustment and/or
service work must be in accordance
with all local codes and must be
performed by a certified service
technician qualified to work on
gas appliances.

D A N G E R

FAILURE TO VENT THIS APPLIANCE
PROPERLY MAY BE HAZARDOUS TO
THE HEALTH OF THE OPERATOR.
Equipment damage, operational
problems and unsatisfactory baking
performance may also be the
consequence of improper venting.
Any damage sustained by a failure to
properly vent this oven are not
covered under warranty.

C A U T I O N

DO NOT USE CIRCULATING FANS

ON THE FLOOR. FLOOR FANS WILL

AFFECT BURNER OPERATION.

C A U T I O N

To prevent malfunction or cause
negative back draft, DO NOT obstruct
exhaust flues or attach any flue
extension that will impede proper
burner operation.

W A R N I N G

Inadequate ventilation, or failure to
ensure an adequate supply of fresh
air will result in a high ambient
temperature at the rear of the
appliance. An excessive ambient
temperature can cause the thermal-
overload protection device on the
blower motor to trip resulting in severe
damage to the blower motor.