Connections and Wiring

19

NetLinx Integrated Controllers

Preparing captive wires

You will need a wire stripper and flat-blade screwdriver to prepare and connect the captive wires.

1.

Strip 0.25 inch (6.35 mm) of insulation off all wires.

2.

Insert each wire into the appropriate opening on the connector (according to the wiring

diagrams and connector types described in this section).

3.

Tighten the screws to secure the wire in the connector. Do not tighten the screws excessively,

doing so may strip the threads and damage the connector.

Wiring length guidelines

The NetLinx Integrated Controllers require auxiliary 12 VDC power from a PSN to operate

properly. The unit should only have one source of incoming power.

Refer to the following tables for the wiring length information used with the different types of

NetLinx Integrated Controllers:

Wiring a power connection

To use the NetLinx 2-pin 3.5 mm mini-Phoenix power supply jack for power transfer from the PSN

power supply, the incoming PWR and GND cables from the PSN must be connected to their

corresponding locations on the 2-pin 3.5 mm mini-Phoenix connector (FIG. 7).

Never pre-tin wires for compression-type connections.

Wiring Guidelines - NI-4000 & NI-3000@ 900 mA

Wire size

Maximum wiring length

18 AWG

130.41 feet (39.75 meters)

20 AWG

82.51 feet (25.15 meters)

22 AWG

51.44 feet (15.68 meters)

24 AWG

32.43 feet (9.88 meters)

Wiring Guidelines - NI-2000 @ 700 mA

Wire size

Maximum wiring length

18 AWG

167.67 feet (51.11 meters)

20 AWG

106.08 feet (32.33 meters)

22 AWG

66.14 feet (20.16 meters)

24 AWG

41.69 feet (12.71 meters)

FIG. 7 2-pin mini-Phoenix connector wiring diagram (direct power)

PWR +

GND -

To the Integrated Controller

NetLinx Power Supply