APPLICATION NOTE AN‐BEI‐H2‐038 

Date: 15/02/12 

 

AN‐BEI‐H2‐038 Modbus RTU Control and Register Mapping 

 

 

 

 

BFI Applications Support Library 

Application Note  AN‐BEI‐P2‐038 
Title 

Modbus RTU Control and Register Mapping

Related Products  Beijer Frequency Inverter H2

Level 

3

 

1 – Fundamental ‐ No previous experience necessary
2 – Basic – Some Basic drives knowledge recommended 
3 – Advanced – Some Basic drives knowledge required 
4 – Expert – Good experience in topic of subject matter recommended

 

 

Overview:  

This document provides information on the Modbus RTU memory mapping that is implemented in the Beijer Frequency Inverter 
H2 drives, detailing which addresses are used to read and write data to / from the Beijer Frequency Inverter H2 in a Modbus RTU 
network. All data registers within the drive are Holding Registers, and can be accessed by means of the Modbus commands 03 
Read Multiple Holding Registers and 06 Write Single Register only.  
 
The Modbus Request PDU specifies the starting register address and the number of registers. In this case, with some Modbus 
Master  Systems,  it  may  be  necessary  to  subtract  1  from  the  register  number  (e.g.  some  systems  treat  holding  register  1  as 
address 0). 
 
The Manufacturer adopts a policy of continuous improvement and whilst every effort has been made to provide accurate and up 
to date information, the information contained in this document should be used for guidance purposes only and does not form 
the part of any contract. 
 

MODBUS RTU Protocol Specification: 

The following table highlights the specification for the Modbus RTU implementation. 
 

Protocol 

Modbus RTU 

Error check 

CRC 

Baud rate 

Parameter Selectable as follows :‐
9600bps, 19200bps, 38400bps, 57600bps, 115200bps (default) 

Data format 

Parameter Selectable as follows :
1 start bit, 8 data bits, 1 stop bits, no parity. (default) 
1 start bit, 8 data bits, 2 stop bits, no parity. 
1 start bit, 8 data bits, 1 stop bits, even parity. 
1 start bit, 8 data bits, 1 stop bits, odd parity. 

Physical signal 

RS 485 (2‐wire)

 

 

 