Parameter 

Register 
Number 

Description 

Range

Scaling 

Type

P2‐18 

218 

User relay 2 output function select 

0: Drive running
1: Drive healthy 
2: Motor at target speed 
3: Motor Speed > 0 
4: Motor Speed > limit 
5: Motor Current > limit 
6: Motor Torque > limit 
7: 2

nd

 Analog input > limit 

 

U16

P2‐19 

219 

User relay 2 upper limit 

P2‐20 to 2000

1 = 0.1% 

U16

P2‐20 

220 

User relay 2 lower limit 

0 to P2‐19

1 = 0.1% 

U16

P2‐21 

221 

Display scaling factor 

0 to 30000

1 = 0.001 

U16

P2‐22 

222 

Display scaling source 

0: Motor Speed
1: Motor Current 
2: 2

nd

 Analog input 

 

U16

P2‐23 

223 

Zero Speed holding time 

0 to 600

1 = 0.1 

U16

P2‐24 

224 

Effective switching frequency 

0 = 4kHz
1 = 8kHz 
2 = 12kHz 
3 = 16kHz 
4 = 24kHz 
5 = 32kHz 

 

U16

P2‐25 

225 

Fast deceleration ramp time  

0 to 3000

1 = 0.1s 

U16

P2‐26 

226 

Spin start enable 

0 : Disabled
1 : Enabled 

U16

P2‐27 

227 

Standby mode 

0 to 2500

1 = 0.1 

U16

P2‐28 

228 

Slave speed scaling control 

0: Disabled
1: Preset by slave speed scaling 
2: P2‐33 scaling + analog in1 offset 
3: P2‐33 scaling + analog in1 scaling 

 

U16

P2‐29 

229 

Slave Speed scaling factor 

‐5000 to 5000

1 = 0.1 

S16

P2‐30 

230 

Analog input 1 format 

0 = 0‐10V
1 = 10‐0V 
2 = ‐10‐10V, 
3 = 0‐20mA,  
4 = t  4‐20mA, 
5 = r  4‐20mA, 
6 = t  20‐4mA,   
7 = r  20‐4mA 

  

U16

P2‐31 

231 

Analog input 1 scaling 

0 to 5000

1 = 0.1 

U16

P2‐32 

232 

Analog input 1 offset 

‐5000 to 5000

1 = 0.1 

S16

P2‐33 

233 

Analog input 2 format 

0 = 0‐10V
1 = 10‐0V 
2 = PTC Thermistor 
3 = 0‐20mA,  
4 = t  4‐20mA, 
5 = r  4‐20mA, 
6 = t  20‐4mA,   
7 = r  20‐4mA 

  

U16

P2‐34 

234 

Analog input 2 scaling 

0 to 5000

1 = 0.1 

S16

P2‐35 

235 

Analog input 2 offset 

‐5000 to 5000

1 = 0.1 

U16

P2‐36 

236 

Start mode select 

0 = Edge‐r
1 = Auto‐0 
2 = Auto‐1 
3 = Auto‐2 
4 = Auto‐3 
5 = Auto‐4 
6 = Auto‐5 

 

U16

P2‐37 

237 

Keypad restart speed 

0: Minimum speed
1: Previous keypad speed 
2: Current running Speed  
3: Preset Speed 8 

 

U16

P2‐38 

238 

Mains loss stop control 

0: Mains loss ride through
1: Coast to Stop 
2: Fast ramp to stop 

 

U16

P2‐39 

239 

Parameter Lock 

0: Unlocked
1: Locked 

 

U16

P2‐40 

240 

Extended parameter access code 
definition 

0 ... 9 999 

 

U16

Advertising