APPLICATION NOTE AN‐BEI‐H2‐038 

Date: 15/02/12 

 

AN‐BEI‐H2‐038 Modbus RTU Control and Register Mapping 

 

61 

User register 11 

03,06

Read/Write

62 

User register 12 

03,06

Read/Write

63 

User register 13 

03,06

Read/Write

64 

User register 14 

03,06

Read/Write

65 

User register 15 

03,06

Read/Write

66 

Analog output 1 user 

03,06

Read/Write

67 

Analog output 2 user 

03,06

Read/Write

68 

Reserved 

03,06

Read/Write

69 

Reserved 

03,06

Read/Write

70 

Relay output 1 user 

03,06

Read/Write

71 

Relay output 2 user 

03,06

Read/Write

72 

Relay output 3 user 

03,06

Read/Write

73 

Relay output 4 user 

03,06

Read/Write

74 

Relay output 5 user 

03,06

Read/Write

75 

User display scaling 

03,06

Read/Write

76 

User display decimal 

03,06

Read/Write

77 

User speed reference 

03,06

Read/Write

78 

User torque reference 

03,06

Read/Write

79 

User ramp 

03,06

Read/Write

80 

Scope index 1,2 

03,06

Read/Write

 Control and Status Register Descriptions: 

Read and write registers 
Register 1: Drive Control Command Word 

15 

14 

13 

12 

11 

10 

7

6

5

4

3

2

1

High byte 

Low byte

Bit 0: 

Run/Stop command: Set to 1 to enable (run) the drive. Set to 0 to disable (stop) the drive. 

 

 

Bit 1:  

Fast stop request. When set to 1 the drive will decelerate to stop using the 2

nd

 deceleration ramp (P2‐25). 

Bit 2: 

Reset Fault Request. Set to 1 in order to reset the drive following a trip / fault.  

         

(Note : This bit must be reset to zero once the fault is cleared to prevent un‐expected reset) 

Bit 3: 

Coast stop request. Set to 1 to issue a coast stop command. 

 
For normal operation, Bit 3 has the highest priority, bit 0 has the lowest priority (bit 3>bit 1>bit 0). For example if the control 
word is set to 0x0009 by the network master, the drive will do a coast stop rather than run. For normal Start / Stop operation, 
bit 0 should be used. 
 
Register 2: Modbus Speed Reference Setpoint 
This register is used to send the speed reference value. The input data is a 16bit signed integer including one decimal place. For 
example, a value of 500 represents a speed reference of 50.0Hz, 123 represents 12.3Hz. It is also possible to reverse the drive by 
sending a negative value in this register. For example, ‐1(0xFFFF) gives ‐0.1Hz. ‐234(0xFF16) gives ‐23.4Hz. 
 
The  input  value  range  is  from  ‐5000  +5000;  however  the  actual  drive  output  frequency  will  be  limited  by  the  minimum  and 
maximum frequencies set in P1‐02 and P1‐01 respectively. 
 
Register 4: Modbus Ramp Control Time 
This register specifies the drive acceleration and deceleration ramp time simultaneously. This value will override the values set in 
parameters P1‐03 and P1‐04 respectively, providing P5‐08 = 1. The input data range is from 0 to 60000 (0.00s to 600.00s) 
 
Read only registers 
Register 6: Drive status and error code 
High byte : Shows the last drive error / fault code. (Valid when the drive is tripped, a list of error codes is shown later in this 
document) 
Low byte : Shows the drive operating status  (0: drive stopped, 1: drive running, 2: drive tipped) 
 
Register 7: Output Frequency 
This register shows the output frequency.  
The data is 16bit integer with one decimal place. E.g. value 123 gives 12.3Hz. Value ‐234 (0xFF16) gives ‐23.4Hz. 
 