APPLICATION NOTE AN‐BEI‐H2‐038 

Date: 15/02/12 

 

AN‐BEI‐H2‐038 Modbus RTU Control and Register Mapping 

 

Group 2 : Extended parameter set (Level 2) 

Parameter 

Register 
Number 

Description 

Range

Scaling 

Type

P2‐01 

201 

Preset speed 1

‐7200 to 7200 (Limited by P1‐01)

3000 = 50.0Hz

S16

P2‐02 

202 

Preset speed 2

‐7200 to 7200 (Limited by P1‐01)

3000 = 50.0Hz

S16

P2‐03 

203 

Preset speed 3

‐7200 to 7200 (Limited by P1‐01)

3000 = 50.0Hz

S16

P2‐04 

204 

Preset speed 4

‐7200 to 7200 (Limited by P1‐01)

3000 = 50.0Hz

S16

P2‐05 

205 

Preset speed 5

‐7200 to 7200 (Limited by P1‐01)

3000 = 50.0Hz

S16

P2‐06 

206 

Preset speed 6

‐7200 to 7200 (Limited by P1‐01)

3000 = 50.0Hz

S16

P2‐07 

207 

Preset speed 7

‐7200 to 7200 (Limited by P1‐01)

3000 = 50.0Hz

S16

P2‐08 

208 

Preset speed 8

‐7200 to 7200 (Limited by P1‐01)

3000 = 50.0Hz

S16

P2‐09 

209 

Skip frequency centrepoint 

0 to 7200 (Limited by P1‐01)

3000 = 50.0Hz

S16

P2‐10 

210 

Skip frequency band 

0 to 7200 (Limited by P1‐01)

3000 = 50.0Hz

S16

P2‐11 

211 

Analog output 1 function select 

Digital Mode (0V or 24V only)
0: Drive running 
1: Drive healthy 
2: Motor at target speed 
3: Motor Speed > 0 
4: Motor Speed > limit 
5: Motor Current > limit 
6: Motor Torque > limit 
7: 2

nd

 Analog input > limit 

(Limit set by P2‐18, P2‐19) 
 
Analog Mode 
8: Speed 
9: Current 
10: Torque 
11: Power 

 

U16

P2‐12 

212 

Analog output 1 format 

0 = 0…10V
1 = 10…0V 
2 = 0‐20mA 
3 = 20‐0mA 
4 = 4‐20mA 
5 = 20‐4mA 

 

U16

P2‐13 

213 

Analog output 2 function select 

Digital Mode (0V or 24V only)
0: Drive running 
1: Drive healthy 
2: Motor at target speed 
3: Motor Speed > 0 
4: Motor Speed > limit 
5: Motor Current > limit 
6: Motor Torque > limit 
7: 2

nd

 Analog input > limit 

(Limit set by P2‐18, P2‐19) 
 
Analog Mode 
8: Speed 
9: Current 
10: Torque 
11: Power 

 

U16

P2‐14 

214 

Analog output 2 format 

0 = 0…10V
1 = 10…0V 
2 = 0‐20mA 
3 = 20‐0mA 
4 = 4‐20mA 
5 = 20‐4mA 

 

U16

P2‐15 

215 

User relay 1 output function select 

0: Drive running
1: Drive healthy 
2: Motor at target speed 
3: Motor Speed > 0 
4: Motor Speed > limit 
5: Motor Current > limit 
6: Motor Torque > limit 
7: 2

nd

 Analog input > limit 

 

U16

P2‐16 

216 

User relay 1 upper limit 

P2‐17 to 2000

1 = 0.1% 

U16

P2‐17 

217 

User relay 1 lower limit 

0 to P2‐16

1 = 0.1% 

U16