Group 4 : motor control parameter set (level 2), Group 5 : fieldbus communications (level 2) – Beijer Electronics AN-BEI-H2-038 User Manual

Page 9

Advertising
background image

APPLICATION NOTE AN‐BEI‐H2‐038 

Date: 15/02/12 

 

AN‐BEI‐H2‐038 Modbus RTU Control and Register Mapping 

 

Group 3 : User PID control (Level 2)        

Parameters 

Register 
Number 

Description 

Range

Scaling 

Type

P3‐01 

301 

User PID Proportional Gain 

1 to 300 

1 = 0.1 

U16

P3‐02 

302 

User PID Integral time constant 

0 to 300 

1 = 0.1 

U16

P3‐03 

303 

User PID Differential time constant 

0 to 100 

1 = 0.01 

U16

P3‐04 

304 

User PID operating mode 

0: Direct
1: Inverse 

 

U16

P3‐05 

305 

User PID reference select 

0: Digital preset (P3‐06)
1: 1

st

 Analog input 

2: 2

nd

 Analog input 

 

U16

P3‐06 

306 

User PID digital reference 

0 to 1000 

1 = 0.1% 

U16

P3‐07 

307 

User PID controller output high limit 

P3‐08 to 1000 

1 = 0.1% 

U16

P3‐08 

308 

User PID controller output low limit 

0 to P3‐07 

1 = 0.1% 

U16

P3‐09 

309 

User PID output control  

0: Digital output limits
1: 1

st

 Analog variable upper limit 

2: 1

st

 Analog variable lower limit 

3: PID output + 1

st

 analog input 

 

U16

P3‐10 

310 

User PID feedback select 

0: 2

nd

Analog input

1: 1

st

 Analog input 

 

U16

P3‐11 

311 

PID error to enable ramps  

0 to 250 

1 = 0.1% 

U16

P3‐12 

312 

PID feedback value display scaling factor 

0 to 50000 

0: Disabled
1 = 0.001 

U16

P3‐13 

313 

PID feedback wake‐up level  

0 to 1000 

1 = 0.1% 

U16

P3‐14 

314 

Standby Active Speed 

0 to 7200 (Limited by P1‐01) 

3000 = 50.0Hz 

U16

 
Group 4 : Motor control parameter set (Level 2) 

Par 

Register 
Number 

Description 

Range

Scaling 

Type

P4‐02 

402 

Motor parameter  
auto‐tune 

0: Disable
1: Enable 

 

U16

 
Group 5 : Fieldbus communications (Level 2) 

Par 

Register 

Description 

Range

Scaling 

Type

P5‐01 

501 

Fieldbus drive address 

0…63

1 = 1 

U16

P5‐03 

503 

Modbus baudrate 

0 = 9.6kbps,
1 = 19.2kpbs, 
2 = 38.4kpbs, 
3 = 57.6kpbs, 
4 = 115 kbps  

 

U16

P5‐04 

504 

Modbus data format 

0 = N‐1 : No Parity 1 stop bit
1 = N‐2 : No parity 2 stop bits 
2 = O‐1 : Odd parity 1 stop bit 
3 = E‐1 : Even parity 1 stop bit 

 

U16

P5‐05 

505 

Comms loss timeout 

0...0.1... 5.0

1 = 0.1s 

U16

P5‐06 

506 

Communications loss action 

0: Trip
1: Ramp to Stop then trip 
2: Ramp to stop (No trip) 
3: Preset speed 8 

1 = 1 

U16

P5‐07 

507 

Fieldbus ramp control 

0: Disable
1: Enable 

1 = 1 

U16

P5‐08 

508 

Anybus module output process data 4 

1: Power (x.xx kW)
2: Digital input status 
3: 2

nd

 analog input (%) 

4. Power stage temperature 

1=1 

U16

 

Advertising