APPLICATION NOTE AN‐BEI‐H2‐038 

Date: 15/02/12 

 

AN‐BEI‐H2‐038 Modbus RTU Control and Register Mapping 

 

Drive Parameters: 

All  User  Adjustable  parameters  in  Groups  1  to  8  can  be  accessed  by  Modbus.  For  further  details  regarding  the  parameter 
functions, please refer to the Beijer Frequency Inverter H2 User Guide. 
Register Type definitions are defined as follows 
WORD  Hexadecimal Word 
U16 

Unsigned 16 Bit Value 

S16 

Signed 16 Bit Value 

 
Group 1 : Basic Parameter Set (Level 1) 

Parameter 

Register 
Number 

Description 

Range

Scaling 

Type

P1‐01 

101 

Max Frequency Limit 

0 to 7200

3000 = 50.0Hz

U16

P1‐02 

102 

Min Frequency Limit 

0 to 7200 (Limited by P1‐01)

3000 = 50.0Hz

U16

P1‐03 

103 

Acceleration Ramp Time 

0 to 6000

300 = 30.0s

U16

P1‐04 

104 

Deceleration Ramp Time 

0 to 6000

300 = 30.0s

U16

P1‐05 

105 

Stop mode 

0: Ramp to Stop
1: Coast to Stop 

 

U16

P1‐06 

106 

Energy optimiser

0: Disable
1: Enable 

 

U16

P1‐07 

107 

Motor rated voltage 

0V, 20V to 250V
0V, 20V to 500V 
0V, 20V to 600V 

230 = 230 V

U16

P1‐08 

108 

Motor rated current 

20% to 100% of drive rated current

1 = 0.1A 

U16

P1‐09 

109 

Motor rated frequency 

25 to 500Hz

50 = 50Hz

U16

P1‐10 

110 

Motor rated speed 

0 to 30 000rpm

1500 = 1500rpm

U16

P1‐11 

111 

V/F Voltage Boost  

Auto,   0.1 to 20%   

‐1 = Auto 
0 = Disabled 
1 = 0.1% 

S16

P1‐12 

112 

Control mode 

0: Terminal mode
1: Keypad mode (Unipolar) 
2: Keypad mode (Bipolar + direction toggle) 
3: User PID mode 
4: Fieldbus (Modbus, Profibus etc.) 
5: Slave mode 

 

U16

P1‐13 

113 

Digital inputs function select 

0: User defined
1...13 See User Guide Table 

 

U16

P1‐14 

114 

Extended Menu Access code 

0 to 30 000

 

U16

 
 

 