Drive error code information – Beijer Electronics AN-BEI-H2-038 User Manual

Page 12

Advertising
background image

APPLICATION NOTE AN‐BEI‐H2‐038 

Date: 15/02/12 

 

AN‐BEI‐H2‐038 Modbus RTU Control and Register Mapping 

12 

 

Drive Error Code Information: 

In the event of a trip, an error code is returned in the High Byte of the drive status word. The fault values correspond to the 
following table. 

Fault 
Code 

No. 

Description 

Fault 
Code 

No.

Description

no‐Flt 

00 

No Fault 

AtF‐01

40

Measured motor stator resistance varies between phases.

OI‐b 

01 

N/A 

 

AtF‐02

41

Measured motor stator resistance is too large. 

OL‐br 

02 

N/A 

AtF‐03

42

N/A

O‐I 

03 

Instantaneous over current

AtF‐04

43

N/A

I.t‐trp 

04 

Motor Thermal Overload (I2t) 

AtF‐05

44

N/A

SAFE‐1 

05 

Safety input circuit error (Processor output)  

AtF‐06

45

Reserved

O‐Volt 

06 

Over voltage on DC bus 

AtF‐07

46

Reserved

U‐Volt 

07 

Under voltage on DC bus 

AtF‐08

47

Reserved

O‐t 

08 

Heatsink over temperature

AtF‐09

48

Reserved

U‐t 

09 

Under temperature 

AtF‐10

49

Reserved

P‐

dEF

 

10 

Factory Default parameters have been loaded 

SC‐F01

50

Modbus comms loss fault 

E‐trip 

11 

External trip 

SC‐F02

51

BACNet comms loss trip 

SC‐ObS 

12 

Optibus comms loss 

SC‐F03

52

Anybus module comms loss trip 

FLt‐dc 

13 

DC bus ripple too high 

SC‐F04

53

IO card comms loss trip 

P‐LOSS 

14 

Input phase loss trip 

SC‐F05

54

Reserved

h O‐I 

15 

Instantaneous over current on drive output.  

SC‐F06

55

Reserved

th‐Flt 

16 

Faulty thermistor on heatsink. 

SC‐F07

56

Reserved

dAtA‐F 

17 

Internal memory fault. (IO)

SC‐F08

57

Reserved

4‐20 F 

18 

4‐20mA Signal Lost 

SC‐F09

58

Reserved

dAtA‐E 

19 

Internal memory fault. (DSP) 

SC‐F10

59

Reserved

U‐dEF 

20 

User Default Parameters Loaded 

OF‐01

60

Internal link to option module loss 

F‐Ptc 

21 

Motor PTC thermistor trip

OF‐02

61

Option module in exceptional condition

FAN‐F 

22 

Cooling Fan Fault 

OF‐03

62

Reserved

O‐hEAt 

23 

Environmental temperature too high  

OF‐04

63

Reserved

O‐torq 

24 

Over torque (HVAC 

OF‐05

64

Reserved

U‐torq 

25 

Under torque (HVAC) 

OF‐06

65

Reserved

Out‐F 

26 

Drive output fault 

OF‐07

66

Reserved

Err‐01 

27 

Reserved 

OF‐08

67

Reserved

Err‐02 

28 

Reserved 

OF‐09

68

Reserved

SAFE‐2 

29 

Safety input circuit error (Buffer output) 

OF‐10

69

Reserved

Enc‐01 

30 

N/A 

PLC‐01

70

Unsupported PLC function block 

Enc‐02 

31 

N/A 

PLC‐02

71

PLC program over size 

Enc‐03 

32 

N/A 

PLC‐03

72

Divide by 0

Enc‐04 

33 

N/A 

PLC‐04

73

Lower limit large than higher limit 

Enc‐05 

34 

N/A 

PLC‐05

74

Table function block index overflow 

Enc‐06 

35 

N/A 

PLC‐06

75

Reserved

Enc‐07 

36 

N/A 

PLC‐07

76

Reserved

Enc‐08 

37 

N/A 

PLC‐08

77

Reserved

Enc‐09 

38 

N/A 

PLC‐09

78

Reserved

Enc‐10 

39 

N/A 

PLC‐10

79

Reserved

 
 
 

 

Advertising