APPLICATION NOTE AN‐BEI‐H2‐038 

Date: 15/02/12 

 

AN‐BEI‐H2‐038 Modbus RTU Control and Register Mapping 

 

Memory Map: 

Table 1: Control and status registers 

Register

 

Upper byte

 

Lower Byte

 

Command

Type

Scaling

1

 

Drive Control Command Word

 

03,06

Read/Write

2

 

Frequency Setpoint (Reference)

03,06

Read/Write

500 = 50.0 Hz 

3

 

Reserved

 

 

 

4

 

Modbus ramp control time

 

03,06

Read/Write

3000 = 30.00 Seconds 

5

 

Reserved

 

 

 

6

 

Error code

 

Drive status

 

03

Read Only

7

 

Output Frequency

 

03

Read Only

500 = 50.0Hz 

8

 

Output Current

 

03

Read Only

100 = 10.0 Amps 

9

 

Reserved

 

 

 

10

 

Output Power

 

03

Read Only

1000 = 10.00kW 

11

 

Digital Input Status

 

03

Read Only

12

 

Rating ID

 

03

Read Only

13

 

Power rating

 

03

Read Only

14

 

Voltage rating

 

03

Read Only

15

 

IO Processor Software Version

 

03

Read Only

100 = 1.00 

16

 

Motor Control Processor Software Version

 

03

Read Only

100 = 1.00 

17

 

Drive Type

 

03

Read Only

18

 

Reserved

 

 

 

19

 

Reserved

 

 

 

20

 

Analog Input 1 Signal Level

 

03

Read Only

1000 = 100.0% 

21

 

Analog Input 2 Signal Level

 

03

Read Only

1000 = 100.0% 

22

 

Pre Ramp Speed Reference (Hz)

03

Read Only

23

 

DC bus Voltage

 

03

Read Only

600 = 600 Volts 

24

 

Drive Temperature

 

03

Read Only

40 = 40°C

25 

Drive Serial Number 4 

03

Read Only

26 

Drive Serial Number 3 

03

Read Only

27 

Drive Serial Number 2 

03

Read Only

28 

Drive Serial Number 1 

03

Read Only

29 

Relay Output Status 

03

Read Only

30 

kWh meter (User) 

03

Read Only

100 = 10.0kWh 

31 

MWh meter (User) 

03

Read Only

100 = 100MWh 

32 

kWh Meter 

03

Read Only

33 

MWh Meter 

03

Read Only

34 

Running time – hour 

03

Read Only

35 

Running time – min/sec 

03

Read Only

36 

Running time since last enable – hour 

03

Read Only

37 

Running time since last enable – min/sec 

03

Read Only

38 

Service time (hours) 

03

Read Only

39 

Room (Control PCB) temperature

03

Read Only

40 

Reserved 

41 

Reserved 

42 

Digital pot reference value 

03

Read Only

43 

P0‐80 

03

Read Only

44 

Reserved 

03

Read Only

45 

Reserved 

03

Read Only

 
Internal Register Access area 

Register

 

Upper byte

 

Lower Byte

 

Command

Type

Scaling

51

 

User register 1

 

03,06

Read/Write

52

 

User register 2

 

03,06

Read/Write

53

 

User register 3

 

03,06

Read/Write

54

 

User register 4

 

03,06

Read/Write

55 

User register 5 

03,06

Read/Write

56 

User register 6 

03,06

Read/Write

57 

User register 7 

03,06

Read/Write

58 

User register 8 

03,06

Read/Write

59 

User register 9 

03,06

Read/Write

60 

User register 10 

03,06

Read/Write