Caution – Comfort-Aire HMB**V*1E SERIES User Manual

Page 12

Advertising
background image

12

Blower Configurations
Selecting Minimum Electric Heat Airflow

The minimum electric heat airflow setting controls the

minimum air flow that will be produced whenever electric

heater kits are used. When the electric heater kit is

energized along with a heat pump, the airflow may be

higher depending on the basic cooling/heat-pump airflow

setting. The minimum electric heat airflow is selected

by the red blower wire on 3-speed models or setting
switches 1,2,3 & 4 on HMB**X*1E models. HMB**V*1E

models automatically set the heating speed based on the
amount of installed heat. The remaining 3 HEAT switches
have no function. Switch settings are listed in Tables 6 or
9 (pages 19 & 21).

NOTE: For HMB**X*1E models,

the

minimum electric heat airflow setting may be set higher,

but must never be set lower than the setting shown in

Table 6 (page 19).

Determining Nominal System Capacity

To select the appropriate airflows for the air handler, the

nominal system capacity must be known. The nominal

system capacity is always the nominal capacity of the

outdoor unit. However, in some situations the nominal

system capacity may not be the same as the nominal

capacity of the air handler. Always refer to the nominal

capacity of the outdoor unit to determine the nominal

system capacity.
NOTE: The CFM values listed in Table 8 (page 20) are

not dependent on duct static pressure. The VSHE motor

automatically compensates for changes in duct static

pressure (within the limits of the motor).

3-Speed Units

The blower speed is preset at the factory for operation

at the same speed for heating and cooling, by using the

jumping terminal on the blower motor and connecting it

to the desired speed with both the red and black wires

connected to the jumping terminal.

NOTE: The control

board is programmed with a 40 second off delay in the

cooling mode for optimum system performance and

efficiency.

CAUTION:

To avoid personal injury or property damage,
make sure the motor leads do not come into
contact with any uninsulated metal components
of the unit.

For optimum system performance and comfort, it may be

necessary to change the factory set speed. See Table 4

(page 17) for airflow data. To change the blower speed:
1. Disconnect all electrical power to the unit and remove

the upper door.

2. Remove the black and red wires from the blower motor

jumping terminal. Discard the blower motor jumping
terminal.

3. Connect the heating speed wire (red) and the cooling

speed wire (black) to the desired blower speed marked
on the terminal block of the blower motor.

• Terminal 4 = Hi speed

• Terminal 5 = Med speed
• Terminal 6 = Low speed

4. Replace the upper door and secure it to the unit.
5. Restore power to the unit.

High Efficiency Units (Variable & Fixed Speed)

IMPORTANT! This air handler has been designed to

give the installer maximum flexibility to optimize system

performance, efficiency, and comfort. Because there are so

many different ways to set up the air handler it is important

to read and follow these directions carefully.

HMB**X*1E, & HMB**V*1E Series air handlers use high

efficiency circulating air motors that come in two variations

and both are controlled differently. The fixed speed motor

control board (Figure 13, page 24) controls the torque

and the variable speed motor control board (Figure 14)

controls the airflow at a constant CFM. Both boards use

the same control board.

Before operation, the air handler must be configured to

match the unit with the system, system options, and climatic

conditions. When configured, the air handler responds

directly to the thermostat inputs, as well as the optional

humidistat (see page 13). During normal operation, the

motor will gradually change speeds during start-up, shut

down, when thermostat inputs change, and when the duct

static pressure changes (vents closed or opened, filter

clogging, etc.). The air handler is configured by setting

the selector switches and removing jumper connectors.

Selecting Basic Heating Airflow

Fixed & variable speed motor control boards (Figures 13

& 14) contain a set of dip switches for setting the blower
speed. For HMB**X*1E Series models, pins 1-4 set the
speed for heating. For HMB**V*1E Series models, the
A/B switch must be set for the appropriate air handler
size (either setting can be used for 48K or 60K BTUH
applications). The airflow is set automatically based on
the amount of installed heat. For both HMB**X*1E, &
HMB**V*1E models, the cooling speed is selected via
switches 5,6,7,& 8. To determine the appropriate switch

settings for your installation, see Tables 5 - 8 (pages 18-20).

Selecting Basic Cooling / Heat Pump Airflow

The basic cooling/heat-pump airflow is controlled by setting
switches 5 - 8 on the motor control board (mounted on the

blower). All airflows for other modes of operation (except

electric heat) are determined by this basic setting. FAN

ONLY would deliver 50% of the selected cooling airflow.

Table 5 lists the basic airflow values versus the airflow

selector switch settings and ranges of basic air flow

settings recommended for each nominal system capacity.

• When operating in the heat pump mode, a higher basic

airflow setting will increase the energy efficiency and
capacity but will also decrease the supply air temperature.

Advertising
This manual is related to the following products: