CONTROL SIGNAL & MODE

OPERATION

TOTAL KW

BOARD ACTION

W

EHEAT

On

5 KW

Stage 1 Heat on instantly
Heat blower on after 3 second delay

10 KW

Stage 1 Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay

15 KW

Stage 1 Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay

20 KW

Stage 1 Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 4 Heat on after 15 seconds delay

Off

Heat stages off instantly
Blower off after 15 second delay

W & Y

AUX HEAT

On

5 KW

Stage 1 Heat on instantly
Cool blower on after 3 second delay

10 KW

Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay

15 KW

Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay

20 KW

Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 4 Heat on after 15 seconds delay

Off

Heat stages off instantly
Heat blower turns off after 40 second delay

G

FAN

On

Cool blower on after 3 second delay

Off

Cool blower off instantly

Y HEAT PUMP

& COOL

On

Cool Blower on after 3 second delay

Off

Cool Blower off after 40 second delay

Table 10. Heating Element Logic for HMB**A*1E Air Handlers