Caution – Comfort-Aire HMB**V*1E SERIES User Manual

Page 4

Advertising
background image

4

Before You Install this Equipment

√ This equipment is securely packaged at the time of

shipment and upon arrival should be carefully inspected

for damage prior to installing the equipment at the job

site. Claims for damage (apparent or concealed) should

be filed immediately with the carrier.

√ it is recommended that the cooling load of the area to

be conditioned should be calculated and a system of

the proper capacity selected.

√ Check the electrical supply and verify the power supply

is adequate for unit operation. The system must be wired

and provided with circuit protection in accordance with

local building codes. If there is any question concerning

the power supply, contact the local power company.

√ Verify the duct system is appropriate for the air handler

being installed. Please note that when replacing an

existing system with lower air-flow, the duct system

may require modification.

Minimum Clearances

• This appliance must be installed in accordance with

clearances listed in Table 1. The air handler must be

installed with ample clearance for easy access to the

air filter, blower assembly, heater assembly, controls,

and vent connections.

• Static pressure drop through louvered openings and

through return air plenums should be considered in

the overall duct design in the determination of the total

external static pressure.

Table 1. Minimum Unit Clearances

INSTALLATION CLEARANCES

Left Side ......... 0 Inches Right Side ...... 0 Inches
Back ............... 0 Inches Front ...........

See Notes

NOTE:

Closet or Alcove Installations:

• Allow 24 in. minimum clearance from front of unit to

nearest wall or partition for servicing. Recommended

clearance is 36 in.

REAR

RIGHT

SIDE

LEFT

SIDE

FRONT

Locating the Air Handler

• Survey the job site to determine the best location for

mounting the unit. Consideration should be given to

availability of electric power, service access, and noise.

• The dimensions of the room or alcove must be able

to accommodate the overall size of the unit and the

installation clearances listed in Table 1. Physical

dimensions for this air handler are shown in Figure 8

(page 15).

• The air handler should be set into position before routing

the refrigerant tubing.

Operation of an Air Handler During Construction

CAUTION:

Failure to follow these instructions will void the
factory warranty and may significantly reduce
the life or the performance of the air handler,
and/or result in other unsafe conditions. It is
the responsibility of the installing contractor
to insure these provisions are met.

Operating an air handler in a construction environment

can cause the appliance a variety of problems. Proper

use of commercial portable space heating equipment

during construction is recommended. This air handler

may be used during construction if it is not in violation of

any applicable codes and the following criteria are met:

• The installation must meet all applicable codes and

be permanently installed according to the instructions

supplied with the air handler including electrical supply

and duct work.

• The air handler must be controlled by a properly installed

thermostat that complies with the current provisions

of the NEC (ANSI/NFPA 70) and all applicable codes

having jurisdiction. Thermostat connections must be

made in accordance with instructions supplied with the

air handler and thermostat. See page 10.

• The installation must include a properly installed filter in

the return air system with no by-pass air. The filter must

be inspected frequently and replaced when necessary.

• Return air must be supplied unrestricted and located

such that dust and gases from construction activity are

not introduced into the circulating air system.

• Before occupying the structure: The filter must be

replaced or cleaned, the duct work must be inspected

and cleaned of any construction debris, and the air

handler must be cleaned and/or repaired if found to

be dirty, damaged, or malfunctioning in any way by

a qualified HVAC technician. The air handler shall be

inspected and approved by applicable local authority

even if this requires redundant inspections.

• The serial number for the air handler used during

construction must be submitted in writing (fax and

email also acceptable). This information will be used to

track the long-term affects of air handler usage during

construction. Proof of this submittal shall be available for

the final inspection of the air handler prior to occupancy.

Advertising
This manual is related to the following products: