CONTROL SIGNAL & MODE

OPERATION

TOTAL KW

BOARD ACTION

W1 & Y/Y2
AUX HEAT

ON

5 KW

Stage 1 Heat on instantly
Cool blower on after 3 second delay

10 KW

Stage 1 Heat on instantly
Cool blower on after 3 second delay

15 KW

Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay

20 KW

Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay

OFF

Heat stages off instantly
Heat blower turns off after 40 second delay

W1, W2 & Y/Y2

AUX HEAT

ON

5 KW

Stage 1 Heat on instantly
Cool blower on after 3 second delay

10 KW

Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay

15 KW

Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 30 seconds delay

20 KW

Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 4 Heat on after 15 seconds delay

OFF

Heat stages off instantly
Heat blower turns off after 40 second delay