Warning – Comfort-Aire HMB**V*1E SERIES User Manual

Page 13

Advertising
background image

13

• For maximum capacity and energy efficiency, select an

airflow at or near the top of the range for that nominal
capacity. See Table 7 (page 19).

• For maximum dehumidification, select an airflow near the

middle or bottom of the range for that nominal capacity.
Additional information on humidity control can be found
in the Humidistat and Delay Setting sections.

• For thermostats with a dehumidifier output, use a field

supplied wire to connect the thermostat’s dehumidifier
output to the terminal marked

DHUM. The thermostat

should be set so that the

DHUM output should be high

(energized) when dehumidification is needed. See also
Dehumidification Options section.

IMPORTANT! If coil icing is observed, the basic cooling/

heat-pump airflow selected may be too low. Verify the

setting selected is within the range shown in Table 7 and

that the the system is properly charged. Please refer to the

instructions supplied with the outdoor unit. If icing continues

to occur, raise the selected airflow one or two steps.
NOTE: Variable speed air handlers with SEER ratings

higher than 15 are matched with a 2-stage cooling outdoor

unit. They are programmed to operate at 75% of the

selected airflow while the system is in the lo-cool mode

and 100% of the selected airflow while in hi-cool mode.

Dehumidification Options
(HMB**X*1E, & HMB**V*1E Series Only)

Both motor control boards (Figures 13 & 14, page 24)

have a

DHUM connection that allows the system to

increase the amount of humidity that is removed from

the circulating air. This is accomplished by reducing the

CFM and allowing the cooling coil to become colder. This

will only occur when there is a call for cooling. There are

many ways that this can be electrically wired.

1. If the room thermostat incorporates a humidity sensor

and

DHUM output, connect the DHUM on the thermostat

to the

DHUM terminal on the motor control board.

2. If using a separate humidistat, connect the

DHUM & R

terminals on the humidistat to the

DHUM & R terminals

on the motor control board of the air handler. In this
option, the

DHUM output of the humidistat must be set

to be normally open and closed when there is a call for
humidification. See Figure 7.

3. If a humidistat is not available, it is an acceptable option

to connect the

R & DHUM terminals on the motor

control board together with a field supplied wire. This
option causes the blower to run at a reduced CFM for
10 minutes after a call for cooling.

NOTE: If outdoor unit

is a heat pump, connect the

O terminal to DHUM.

DHUM

R

R

DHUM

HUMIDISTAT

MOTOR

CONTROL BOARD

Figure 7. DHUM Wiring Configuration

UNIT MAINTENANCE

Proper maintenance is most important to achieve the best

performance from an air handler. Some of the components

and their locations are shown in Figure 9 (page 16). If

any component of the air handler must be replaced, use

only factory authorized replacement parts specified in the

Replacement Parts List provided online.

WARNING:

ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD

Failure to follow safety warnings exactly could

result in serious injury or property damage.
Improper servicing could result in dangerous

operation, serious injury, death or property

damage.
• Before servicing, disconnect all electrical power

to the air handler.

• When servicing controls, label all wires prior

to disconnecting. Reconnect wires correctly.

• Verify proper operation after servicing.

• These maintenance instructions are primarily intended

to assist qualified technicians experienced in the proper

maintenance and operation of this appliance.

• Always reinstall the doors on the air handler after

servicing or cleaning/changing the filters. Do not operate

the air handler without all doors and covers in place.

• To achieve the best performance and minimize equipment

failure, it is recommended that a yearly maintenance

checkup be performed. At a minimum, this check should

include the following items:

Air Filter(s)

WARNING:

Never operate the air handler without a filter in
place. Dust and lint in the return air can build
up on internal components, resulting in loss of
efficiency, equipment damage, and possible fire.

Inspect and replace the air filter at the beginning of heating

and cooling season. It is recommended that the filter

be cleaned or replaced monthly. Newly built or recently

renovated homes may require more frequent changing

until the construction dust has minimized. Filters designed

to remove smaller particles such as pollen, may require

additional maintenance.

Blower Compartment

Dirt and lint can create excessive loads on the motor

resulting in higher than normal operating temperatures

and shortened service life. It is recommended that the

blower compartment be cleaned of dirt or lint that may

have accumulated in the compartment or on the blower

and motor as part of the annual inspection.

Advertising
This manual is related to the following products: