Warning – Comfort-Aire HMB**V*1E SERIES User Manual

Page 5

Advertising
background image

5

• It is good practice to seal all connections and joints

with industrial grade sealing tape or liquid sealant.

Requirements for sealing ducts vary from region to

region. Consult with local codes for requirements specific

to your area.

Supply Air Connections

The supply air must be delivered to the heated space by

duct(s) secured to the blower’s casing, running full size

and without interruption. Tape or seal all seams if required

by local code.

Upflow & Horizontal Applications: To attach the supply air

duct, bend the flanges (on top of the unit) outward 90°

with a pair of wide duct pliers. Position the duct on top of

the blower and secure together with sheet metal screws.

Downflow Applications: Position the blower over the duct

and secure together with sheet metal screws.

Return Air Connections

The return air must be delivered to the blower by duct(s)

secured to the casing, running full size and without

interruption. Tape or seal all seams if required by local code.

Upflow & Horizontal Applications: Position the blower over

the duct and secure together with sheet metal screws.

Downflow Applications: To attach the supply air duct,

bend the furnace flanges outward 90° with a pair of wide

duct pliers. Position the duct on top of the cased coil and

secure together with sheet metal screws.

Acoustical Duct Work
• Certain installations may require the use of acoustical

lining inside the supply duct work. Acoustical insulation

must be in accordance with the current revision of the

Sheet Metal and Air Conditioning Contractors National

Association (SMACNA) application standard for duct

liners. Duct lining must be UL classified batts or blankets

with a fire hazard classification of FHC-25/50 or less.

• Fiber duct work may be used in place of internal duct

liners if the fiber duct work is in accordance with the

current revision of the SMACNA construction standard

on fibrous glass ducts. Fibrous duct work and internal

acoustical lining must be NFPA Class 1 air ducts when

tested per UL Standard 181 for Class 1 ducts.

• Damping ducts, flexible vibration isolators, or pleated

media-style filters on the return air inlet of the air
handler may be used to reduce the transmission of
equipment noise eminating from the air handler. These
treatments can produce a quieter installation, particularly
in the heated space. However, they can increase the
pressure drop in the duct system. Care must be taken
to maintain the proper maximum pressure rise across
the air handler, temperature rise and flow rate. This
may mean increasing the duct size and/or reducing the
blower speed. These treatments must be constructed
and installed in accordance with NFPA and SMACNA
construction standards. Consult with local codes for
special requirements. For best sound performance, be
sure to install all the needed gaskets and grommets

Plenums & Air Ducts
• Plenums and air ducts should be installed in

accordance with the standards of the National Fire
Protection Association Standard for Installation of
Air Conditioning Systems (NFPA 90A), Standard for
Installation of Residence Type Warm Air Heating
and Air Conditioning Systems (NFPA 90B), and all
applicable local codes. NFPA publications are available
by writing to: National Fire Protection Association,
Batterymarch Park, Quincy, ME 02269 or visit
www.NFPA.org online.

WARNING:

All return ducts must be secured to the air
handler using appropriate methods. All return
ducts must be adequately sealed. When return
air is provided through the bottom of the unit,
the joint between the air handler and the return
air plenum must be air tight.

Return air and circulating air ducts must not be
connected to any other heat producing device
such as a fireplace insert, stove, etc. This may
result in fire, explosion, carbon monoxide
poisoning, personal injury, or property damage.

• Design the duct work according to methods described

by the Air Conditioning Contractors of America (ACCA).

• This unit is designed only for use with a return and supply

duct. The return air duct must have the same free area

as the opening provided on the air handler. The ducts

should be appropriately sized to the capacity of the air

handler to ensure its proper airflow rating.

• This unit should be located with consideration of

minimizing the length of the supply and return ducts.

See Tables 4 - 8 (pages 17 - 20) and the rating plate

for proper circulating airflow data.

• Whenever the supply or return air ducts pass through

the floor, a 1/4” thick noncombustible resilient gasket

must be used between the duct, unit and floor

• Use transition fittings if the supply and/or return air

openings of the unit do not match the duct openings.

These transitions should be dimensioned in accordance

with standard practice as specified in the ASHRAE

recommendations for duct transitions.

• The supply air ductwork must be of noncombustible

material for the first 24 inches from the unit. Some

installations with a short, straight run from the unit to

the first branch takeoff may require acoustical lining

inside the supply air ductwork. Consult with local codes

for requirements specific to your area.

• Flexible connectors may be used between the unit

and the ductwork to prevent transmission of vibration

from the unit to the structure. If electric heater kits are

installed, heat resistant material must be used for the

flexible connector at the supply air end of the unit.

Advertising
This manual is related to the following products: