Comfort-Aire HMB**V*1E SERIES User Manual

Page 29

Advertising
background image

29

CONTROL SIGNAL & MODE

OPERATION

TOTAL KW

BOARD ACTION

W1 only

EHEAT

ON

5 KW

Stage 1 Heat on instantly
Heat blower on after 3 second delay

10 KW

Stage 1 Heat on instantly
Heat blower on after 3 second delay

15 KW

Stage 1 Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 second delay

20 KW

Stage 1 Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 second delay
Stage 3 Heat on after 10 second delay

OFF

Heat stages off instantly
Blower off after 15 second delay

W1 & W2

EHEAT

ON

5 KW

Stage 1 Heat on instantly
Heat blower on after 3 second delay

10 KW

Stage 1 Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay

15 KW

Stage 1 Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay

20 KW

Stage 1 Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 4 Heat on after 15 seconds delay

OFF

Heat stages off instantly
Blower off after 15 second delay

Table 11. Heating Element Logic for HMB**X*1E & HMB**V*1E Series Air Handler

Advertising
This manual is related to the following products: