Comfort-Aire HMB**V*1E SERIES User Manual

Page 19

Advertising
background image

19

HMB36VA1E

CFM

SWITCH SETTINGS

(1 = ON, 0 = OFF)

NOMINAL

CAPACITY

5

6

7

8

525

0

0

0

0

1.5 T

ON

560

0

0

0

1

600

0

0

1

0

625

0

0

1

1

700

0

1

0

0

2 T

ON

750

0

1

0

1

800

0

1

1

0

2.5 T

ON

850

0

1

1

1

875

1

0

0

0

890

1

0

0

1

930

1

0

1

0

950

1

0

1

1

1000

1

1

0

0

3 T

ON

1050

1

1

0

1

1125

1

1

1

0

1200

1

1

1

1

HMB48VB1E

HMB60VC1E

CFM

SWITCH SETTINGS

(1 = ON, 0 = OFF)

NOMINAL

CAPACITY

CFM

SWITCH SETTINGS

(1 = ON, 0 = OFF)

NOMICAL

CAPACITY

5

6

7

8

5

6

7

8

525

0

0

0

0

1.5 T

ON

1100

0

0

0

0

3 T

ON

560

0

0

0

1

1200

0

0

0

1

3.5 T

ON

600

0

0

1

0

1250

0

0

1

0

650

0

0

1

1

2 T

ON

1300

0

0

1

1

4 T

ON

700

0

1

0

0

1350

0

1

0

0

750

0

1

0

1

1400

0

1

0

1

800

0

1

1

0

2.5 T

ON

1450

0

1

1

0

850

0

1

1

1

1500

0

1

1

1

875

1

0

0

0

1550

1

0

0

0

950

1

0

0

1

1600

1

0

0

1

5 T

ON

1050

1

0

1

0

3 T

ON

1650

1

0

1

0

1150

1

0

1

1

3.5 T

ON

1700

1

0

1

1

1250

1

1

0

0

1750

1

1

0

0

1350

1

1

0

1

4 T

ON

1800

1

1

0

1

1400

1

1

1

0

1900

1

1

1

0

1600

1

1

1

1

2000

1

1

1

1

FURNACE MODELS

Nominal Electic Heat KW

5

8

10

15

20

HMB36XA1E

800

900

1000

1300

N/A

HMB48XB1E

900

1000

1100

1300

1500

HMB60XC1E

1000

1100

1200

1400

1600

NOTE: See Table 6 for appropriate switch settings for these airflows.

Table 6. Minimum Heating Airflow Settings (in CFM)

for HMB**X*1E Series Air Handlers

Table 7. Recommended Cooling Airflow Settings for HMB**V*1E Series Air Handlers

Advertising
This manual is related to the following products: