SPECIFICATIONS (cont)

UNIT SIZE

155

180

240

FURNACE SECTION

Low Heat

High Heat

High Heat

Low Heat

High Heat

Rollout Switch Cutout

Temp (F)††

190

190

190

190

190

Burner Orifice Diameter

(in. ...drill size)

Natural Gas

.113...33

.113...33

.113...33

.113...33

.113...33

Pilot Orifice Diameter

(in. ...drill size)

Natural Gas

0.55...54

.055...54,
.041...59

.055...54,

.041..59

.055...54,
.041...59

.071...50,
.071...50

Thermostat Heat Anticipator

Setting (amps)

208/230 v Stage 1

0.98

0.98

0.98

0.98

0.98

Stage 2

0.44

0.44

0.44

0.44

460 v Stage 1

1.20

1.20

1.20

1.20

1.20

Stage 2

0.60

0.60

0.60

0.60

Gas Input (Btuh) Stage 1

154,000

115,500

115,500

115,500

242,500

Stage 2

231,000

270,000

270,000

485,000

Efficiency (Steady

State) (%)

80

80

80

80

80

Temperature Rise Range

15-45

25-55

15-45

15-45

35-65

Manifold Pressure

(in. wg)

Natural Gas

3.5

3.5

3.5

3.5

3.5

Gas Valve Pressure Range

Psig

0.180-0.487

0.180-0.487

0.180-0.487

0.180-0.487

0.180-0.487

in. wg

5.0-13.5

5.0-13.5

5.0-13.5

5.0-13.5

5.0-13.5

Gas Valve Quantity

2

2

2

2

2

Field Gas Connection

Size (in.)

3

4

3

4

3

4

3

4

3

4

HIGH-PRESSURE SWITCH (psig)

Standard Compressor

Internal Relief

Cutout

426

Reset (Auto.)

320

LOW-PRESSURE SWITCH (psig)

Cutout

7

Reset (Auto.)

22

FREEZE PROTECTION

THERMOSTAT (F)

Opens

30 ± 5

Closes

45 ± 5

OUTDOOR-AIR INLET SCREENS

Cleanable

Quantity...Size (in.)

2...20 x 25 x 1
1...20 x 20 x 1

RETURN-AIR FILTERS

Throwaway

Quantity...Size (in.)

4...20 x 20 x 2
4...16 x 20 x 2

LEGEND

Al

Aluminum

Bhp — Brake Horsepower

*Evaporator coil fin material/condenser coil fin material.

†Low-heat weight/high-heat weight.

**Weight of 14-in. roof curb.

††Rollout switch is manual reset.

NOTE: The 581A units have a low-pressure switch (standard) located
on the suction side.