Fan rpm at motor pulley settings, Electrical data – Bryant 581A User Manual

Page 19

Advertising
background image

FAN RPM AT MOTOR PULLEY SETTINGS*

UNIT
581A

MOTOR PULLEY TURNS OPEN

0

1

2

1

1

1

2

2

2

1

2

3

3

1

2

4

4

1

2

5

5

1

2

6

155

1526

1492

1459

1426

1393

1360

1326

1293

1260

1227

1194

180

1494

1472

1451

1430

1408

1387

1366

1345

1323

1302

1281

1259

1238

240

1536

1515

1493

1472

1451

1430

1408

1387

1366

1344

1323

*Approximate fan rpm shown.

†Do not run this fan at less than 1 turn open, as it will exceed the maximum

allowable rpm of 1550.

ELECTRICAL DATA

UNIT
581A

NOMINAL
VOLTAGE

(3 Ph,

60 Hz)

VOLTAGE

RANGE

COMPRESSOR

OFM

IFM

POWER

EXHAUST

COMBUSTION

FAN MOTOR

POWER SUPPLY

DISCONNECT

SIZE

No. 1

No. 2

Min Max RLA LRA RLA LRA Qty

FLA

(ea)

LRA

(ea)

Hp

FLA

LRA

FLA LRA

FLA

MCA

MOCP*

FLA

LRA

155

208/230

187

254

39.7

228

3

1.7

3.8

3.7 10.5/10.5 84.5/84.5

0.57

65/65

100/100

64/64

324/324

4.6

18.8

0.57

70/70

100/100

70/70

343/343

460

414

508

19.9

114

3

0.8

1.9

3.7

4.8

42.3

0.30

32

50

32

162

2.3

6.0

0.30

34

50

34

168

180

208/230

187

254

28.2

160

28.2

160

3

1.7

24.8

5

15.8/15.8

105/91

0.57

84/84

110/100

90/90

499/485

4.6

18.8

0.57

89/89

110/110

95/95

518/504

460

414

508

14.1

80

14.1

80

3

0.8

10.8

5

7.9

46

0.30

42

50

45

238

2.3

6.0

0.30

44

50

47

244

240

208/230

187

254

35.6

198

35.6

198

2

5.5

24.8 10 28.0/28.0

193/168

0.57

119/119 150/150 127/127 639/614

4.6

18.8

0.57

124/124 150/150 133/133 657/632

460

414

508

17.8

99

17.8

99

2

2.8

10.8 10

14.6

84

0.30

60

70

65

304

2.3

6.0

0.30

63

80

67

310

LEGEND

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

*This is the maximum size permissible; smaller fuse size may be used where con-

ditions permit.

NOTES: In compliance with NEC requirements for multimotor and combination
load equipment (refer to NEC Articles 430 and 440), the overcurrent protective de-
vice for the unit shall be fuse or HACR breaker. The Canadian units may be fuse
or circuit breaker.

19