DIMENSIONAL DRAWING — 581A240

UNIT
581A

CORNER WEIGHT*

DIMENSIONS

A

B

C

D

A

B

C

D

E

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Ft-in.

mm

Ft-in.

mm

Ft-in.

mm

Ft-in.

mm

Ft-in.

mm

240 270

523

237

541

245

574

260

596

270

3-4

1016

3-7

1092

0-3

76

6-11

1

2

2121

1-7

13

16

504

240 485

465

211

486

220

725

329

737

334

4-2

1270

3-5

1041

0-4

1

2

114

8- 7

1

4

2623

3-3

5

8

1006

*Weights are for unit only and do not include options or crating.

UNIT
581A

MAXIMUM SHIPPING

WEIGHT

Lb

Kg

240 270

2514

1140

240 485

2793

1267

NOTES:
1. Dimensions in (

) are in millimeters.

2.

Center of gravity.

3.

Direction of airflow.

4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance:

a. Rear: 7

Ј

0

Љ

(2134) for coil removal. This dimension

can be reduced to 4

Ј

0

Љ

(1219) if conditions permit

coil removal from the top.

b. 4

Ј

0

Љ

(1219) to combustible surfaces, all four sides

(includes between units).

c. Left side: 4

Ј

0

Љ

(1219) for proper condenser coil

airflow.

d. Front: 4

Ј

0

Љ

(1219) for control box access.

e. Right side: 4

Ј

0

Љ

(1219) for proper operation of

damper and power exhaust (if so equipped).

f. Top: 6

Ј

0

Љ

(1829) to assure proper condenser fan

operation.

g. Bottom: 14

Љ

(356) to combustible surfaces (when not

using curb).

h. Control box side: 3

Ј

0

Љ

(914) to ungrounded surfaces

(non-combustible).

i. Control box side: 3

Ј

6

Љ

(1067) to block or concrete

walls, or other grounded surfaces.

j. Local codes or jurisdiction may prevail.

6. With the exception of clearance for the condenser coil

and the damper/power exhaust as stated in Note No. 5,
a removable fence or barricade requires no clearance.

7. Dimensions are from outside of corner post. Allow

0

Ј

-

5

16

Љ

(8) on each side for top cover drip edge.