Bryant 581A User Manual

Page 24

Advertising
background image

APPLICATION DATA (cont)

EVAPORATOR-FAN MOTOR PERFORMANCE

UNIT
581A

UNIT

VOLTAGE

MAXIMUM

ACCEPTABLE
CONTINUOUS

BHP*

MAXIMUM

ACCEPTABLE

OPERATING

WATTS

MAXIMUM

AMP DRAW

155

208/230

4.25

3775

10.5

460

4.8

180

208/230

5.90

5180

15.8

460

7.9

240

208/230

10.20

9510

28.0

460

11.80

11,000

14.6

LEGEND

Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the

full horsepower range of the motors can be utilized with confidence.

Using your fan motors up to the horsepower ratings shown in this table
will not result in nuisance tripping or premature motor failure. Unit war-
ranty will not be affected.

Concentric Duct Air Distribution

NOTE: Do not drill in this area; damage to basepan may result in
water leak.

Concentric Duct Details

NOTE: Dimensions A, A

Ј

and B, B

Ј

are obtained from field-

supplied ceiling diffuser.

Shaded area indicates block-off panels.

24

Advertising