Bryant 581A User Manual

Page 17

Advertising
background image

AIR DELIVERY (cont)

581A240 (20 TON)

Airflow

(Cfm)

Standard Belt-Drive Motor

External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

1.0

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

6000

800

1732

1.88

891

2047

2.22

975

2376

2.58

1055

2728

2.96

1133

3104

3.37

6500

853

2134

2.32

939

2471

2.68

1018

2819

3.06

1094

3185

3.46

1167

3573

3.88

7000

907

2596

2.82

989

2957

3.21

1064

3324

3.61

1136

3707

4.02

1205

4107

4.46

7500

962

3123

3.39

1039

3507

3.81

1111

3895

4.23

1179

4295

4.66

1245

4710

5.11

8000

1017

3717

4.04

1091

4126

4.48

1160

4536

4.93

1225

4954

5.38

1287

5386

5.85

8500

1072

4385

4.76

1143

4818

5.23

1209

5250

5.70

1271

5688

6.18

1332

6137

6.66

9000

1128

5129

5.57

1196

5587

6.07

1260

6042

6.56

1323

6501

7.06

1377

6968

7.57

9500

1185

5955

6.47

1250

6437

6.99

1311

6915

7.51

1369

7395

8.03

1424

7881

8.56

10000

1241

6865

7.45

1304

7372

8.00

1363

7873

8.65

1419

8376

9.09

1472

8882

9.64

581A240 (20 TON) (cont)

Airflow

(Cfm)

Standard Belt-Drive Motor

External Static Pressure (in. wg)

1.2

1.4

1.6

1.8

2.0

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

6000

1208

3504

3.80

1282

3926

4.26

1353

4368

4.74

1421

4826

5.24

1488

5299

5.75

6500

1239

3983

4.32

1308

4415

4.79

1376

4866

5.28

1442

5337

5.79

1507

5823

6.32

7000

1273

4529

4.92

1339

4970

5.40

1403

5432

5.90

1467

5911

6.42

1520

6339

6.88

7500

1309

5143

5.58

1372

5597

6.08

1434

6067

6.59

1494

6558

7.12

1548

7014

7.62

8000

1349

5833

6.33

1409

6297

6.84

1467

6779

7.36

1529

7313

7.94

8500

1390

6600

7.17

1447

7077

7.68

1504

7571

8.22

9000

1433

7446

8.08

1488

7938

8.62

9500

1478

8378

9.10

10000

1524

9396

10.20

LEGEND

Bhp

Brake Horsepower Input to Fan

FIOP

Factory-Installed Option

Watts — Input Watts to Motor

NOTES:
1. Boldface indicates standard operating range.
2. All other numbers indicate field-supplied drive required.
3.

indicates maximum bhp/watts of standard motor and drive.

4. Factory shipped motor drive range is 1323 to 1579 rpm. Other rpms

require a field-supplied drive.

5. Static pressure losses (i.e., economizer) must be added to external

static pressure before entering Air Delivery table. See page 18 for
accessory/FIOP static pressure information.

6. Interpolation is permissible. Do not extrapolate.
7. Maximum continuous bhp is 10.2 for 208/230-v units and 11.8 for

460-v units. The maximum continuous watts are 9510 for the 208/
230-v units and 11,000 for the 460-v unit. Extensive motor and drive
testing on these units ensures that the full horsepower range of the
motor can be utilized with confidence. Using your fan motors up to
the wattage ratings shown will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected.

NOTE: The 389210-201, 389211-201 high static regain
adapter accessories may be used to provide horizontal
supply/return.

NOTE: The 389210-201, 389211-201 horizontal supply/
return adapter accessories improve 581A fan perfor-
mance by increasing external static pressure by amount
shown above.

Horizontal Supply/Return Fan Performance

With 389210-201 or 389211-201 High Static Regain Adapter

17

Advertising