Bryant 581A User Manual

Page 13

Advertising
background image

GROSS COOLING CAPACITIES (cont)

581A180 (15 TON)

Air Entering

Evaporator

Air Entering Condenser (F)

75

85

95

Cfm

BF

Ewb

(F)

Capacity MBtuh

Compressor

kW

Capacity MBtuh

Compressor

kW

Capacity MBtuh

Compressor

kW

Total

Sensible

Total

Sensible

Total

Sensible

4500

0.03

72

224.0

108.0

12.94

216.0

105.0

14.34

206.0

101.2

15.64

67

206.0

133.2

12.62

196.2

129.6

13.94

186.4

125.6

15.16

62

186.2

156.2

12.26

177.0

153.0

13.48

167.6

148.8

14.70

5250

0.03

72

230.0

113.2

13.06

220.0

109.4

14.42

210.0

107.0

15.82

67

212.0

143.0

12.74

202.0

139.6

14.08

191.6

135.6

15.34

62

191.8

171.4

12.38

182.6

166.4

13.66

172.6

162.0

14.90

6000

0.04

72

234.0

117.8

13.16

224.0

114.8

14.52

214.0

112.4

15.96

67

216.0

152.0

12.84

206.0

148.8

14.20

195.6

144.8

15.46

62

196.4

182.8

12.50

186.8

179.2

13.80

177.0

174.0

15.02

6750

0.05

72

236.0

122.8

13.22

226.0

119.6

14.60

216.0

115.8

15.94

67

218.0

160.8

12.92

210.0

157.4

14.28

198.4

153.4

15.56

62

200.0

194.2

12.60

190.6

190.2

13.92

182.6

182.2

15.20

7500

0.05

72

238.0

127.8

13.28

228.0

124.0

14.66

216.0

120.4

16.02

67

220.0

168.4

12.96

212.0

165.6

14.34

200.0

161.6

15.62

62

204.0

204.0

12.70

196.2

196.0

14.04

187.6

187.6

15.34

581A180 (15 TON) (cont)

Air Entering

Evaporator

Air Entering Condenser (F)

105

115

125

Cfm

BF

Ewb

(F)

Capacity MBtuh

Compressor

kW

Capacity MBtuh

Compressor

kW

Capacity MBtuh

Compressor

kW

Total

Sensible

Total

Sensible

Total

Sensible

4500

0.03

72

194.6

97.4

16.92

183.0

92.6

18.02

171.2

88.6

19.08

67

176.4

121.8

16.38

166.4

117.6

17.48

155.8

113.0

18.42

62

156.8

143.6

15.84

149.0

140.0

16.86

139.4

135.4

17.84

5250

0.03

72

198.4

102.0

17.02

186.4

97.6

18.18

172.6

92.2

19.16

67

181.4

131.0

16.54

170.8

127.0

17.66

159.0

121.6

18.60

62

163.0

157.6

16.02

154.0

152.4

17.04

145.4

145.2

18.12

6000

0.04

72

200.0

106.8

17.12

188.6

102.6

18.30

176.2

98.0

19.38

67

184.8

140.6

16.70

173.4

136.0

17.80

161.4

129.8

18.74

62

168.2

168.2

16.22

160.0

160.0

17.34

151.4

151.2

18.40

6750

0.05

72

202.0

111.8

17.22

190.8

107.6

18.40

178.2

103.0

19.50

67

187.2

149.0

16.80

175.4

144.2

17.88

163.4

138.0

18.90

62

174.0

174.0

16.44

165.4

165.2

17.58

156.2

155.8

18.64

7500

0.05

72

204.0

116.4

17.28

192.2

112.4

18.48

178.8

106.8

19.54

67

188.8

157.2

16.86

177.0

151.8

17.98

164.8

145.4

18.98

62

179.0

178.8

16.60

169.6

169.4

17.74

159.6

159.6

18.82

LEGEND

BF

Bypass Factor

Edb

Entering Dry Bulb

Ewb

Entering Wet Bulb

kW

Compressor Motor Power Input

MBtuh — Btuh in thousands

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

sensible capacity (1000 x MBtuh)

t

= t

ldb

edb

1.10 x cfm

t

= Wet-bulb temperature corresponding to enthalpy of air

lwb

leaving evaporator coil (h

)

lwb

total capacity (1000 x MBtuh)

h

= h

lwb

ewb

4.5 x cfm

Where: hewb = Enthalpy of air entering evaporator coil.

3. The sensible heat capacity is based on 80 F entering dry-bulb (edb)

temperature of air entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from the sensible heat
capacity.
Above 80 F edb, add (corr factor x cfm) to the sensible heat
capacity.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

13