APPLICATION DATA

1. Ductwork — Ductwork should be attached to the curb on all

units. Interior installation may proceed before unit is set in
place on roof. If ductwork will be attached to the unit, do not
drill in condensate drain pan area — leaks may result. See
figures on page 24 for information on field-installed concen-
tric ductwork when applicable.

2. Thru-The-Curb Service Connections — Roof curb connec-

tions allow field power wires, control wires, and gas supply
to enter through the roof curb opening.

3. Thermostat — Use of 2-stage cooling thermostat is

required.

4. Heating-to-Cooling Changeover — All units are automatic

changeover from heating to cooling when automatic
changeover thermostat and subbase are used.

5. Airflow — Units are draw-thru on cooling and blow-thru on

heating.

6. Maximum Airflow — To minimize the possibility of conden-

sate blow-off from evaporator, airflow through units should
not exceed 500 cfm/ton.

7. Minimum Airflow — The minimum airflow for cooling is

300 cfm/ton.

8. Minimum Ambient Cooling Operation Temperature — Units

are designed to operate at outdoor temperatures down to
35 F. To operate at lower outdoor-air temperatures, see
Trade Prices for appropriate accessories, or contact your
local representative.

9. Maximum Operating Outdoor-Air Temperature — For cool-

ing, this temperature is 120 F (180) or 125 F (155, 240).

10. High Altitude — A change to the gas orifice may be required

at high altitudes. Refer to Altitude Compensation chart
below.

ALTITUDE COMPENSATION*

ELEVATION

(Ft)

NATURAL GAS

Orifice Size†

0-2,000

33

2,000

35

3,000

35

4,000

36

5,000

36

6,000

37

7,000

38

8,000

38

9,000

40

10,000

41

11,000

43

12,000

44

13,000

44

14,000

45

*As the height above sea level increases, there is less oxygen per

cubic ft of air. Therefore, heat input rate should be reduced at higher
altitudes.

†Orifices available through your distributor.

11. Minimum Temperature — Air entering the heat exchanger in

heating is 50 F continuous and 45 F intermittent.

12. Internal Unit Design — Due to the internal design (draw-

thru over the motor), air path, and specially designed mo-
tors, the full horsepower (maximum continuous bhp) listed
in the Specifications table and the notes following each Air
Delivery table can be utilized with extreme confidence.

Using the motors with the values listed in the Specifications
table

will not

result in nuisance tripping or premature motor

failure. The unit warranty will not be affected.

OPTION AND ACCESSORY LIST

ITEM

FACTORY-

INSTALLED

OPTION

FIELD-

INSTALLED

ACCESSORY

Integrated Economizer

X

X

Manual Outdoor-Air Damper

X

Two-Position Damper

X

Barometric Relief Damper

X

Roof Curbs (Horizontal and Vertical)

X

Horizontal Adapter

X

Thermostats and Subbases

X

Power Exhaust

X

Head Pressure Control Device

X

Low-Ambient Kit

X

Time Guard

II Control Circuit

X

Enthalpy Control Sensor

X

Winter Start Time-Delay
Relay

X

ALTITUDE DERATING FACTOR*

ELEVATION

(Ft)

MAXIMUM HEATING VALUE

(Btu/ft

3

)

0-2,000

1,100

2,001-3,000

1,050

3,001-4,000

1,000

4,001-5,000

950

5,001-6,000

900

*Derating of the unit is not required unless the heating value of the gas

exceeds the values listed in the table above, or if the elevation exceeds
6000 ft. Derating conditions must be 4% per thousand ft above sea
level. For example, at 4000 ft, if the heating value of the gas exceeds
1000 Btu/ft

3

, the unit will require a 16% derating. For elevations above

6000 ft, the same formula applies. For example, at 7000 ft, the unit will
require a 28% derating of the maximum heating value per the National
Fuel Gas Code.