SOUND POWER (Total Unit)

UNIT
581A

SOUND

RATING-BELS

(60 Hz)

A-WEIGHTED

(dB)

OCTAVE BANDS

63

125

250

500

1000

2000

4000

8000

155

8.8

87.3

87.1

89.9

86.4

84.0

82.7

79.0

73.9

68.6

180

8.9

88.0

95.7

88.9

87.2

85.2

91.9

79.5

72.7

66.0

240

9.5

94.1

90.6

87.2

89.9

86.2

85.8

81.0

75.6

69.6

Bels — Sound Levels (1 bel = 10 decibels)

NOTE: All values are in dB unless otherwise noted.

AIR QUANTITY LIMITS

UNIT 581A

MINIMUM CFM

MAXIMUM CFM

155

3750

6,250

180

4500

7,500

240

6000

10,000

ACCESSORY/FIOP ECONOMIZER STATIC PRESSURE (in. wg)

UNIT
581A

UNIT

VOLTAGE

CFM

ECONOMIZER

PRESSURE DROP

155,180

All

3,750

.03

4,000

.03

5,000

.05

6,000

.07

7,500

.10

240

All

6,000

.07

7,200

.09

9,000

.11

10,000

.12

LEGEND

FIOP — Factory-Installed Option
NOTES:
1. The factory-assembled horizontal adapter substantially improves fan performance. See graph on

page 17.

2. The static pressure must be added to external static pressure. The sum and the evaporator

entering-air cfm should then be used in conjunction with the Air Delivery table to determine blower
rpm, bhp, and watts.

Fan Performance Using Accessory Power Exhaust

18