HEATING CAPACITIES AND EFFICIENCIES

UNIT 581A

HEATING INPUT

(Btuh)

Stage 2/Stage 1

OUTPUT CAPACITY

(Btuh)

TEMPERATURE

RISE (F)

STEADY-STATE

EFFICIENCY

(%)

MINIMUM

HEATING

CFM

155 154

—/154,000

123,000

15-45

80

2485

155 231

231,000/115,500

185,000

25-55

80

3057

180 270

270,000/115,500

216,000

15-45

80

4364

240 270

270,000/115,500

216,000

15-45

80

4364

240 485

485,000/242,500

388,000

35-65

80

5427

CAPACITY RATINGS

UNIT 581A

NOMINAL

TONS

NET COOLING

TOTAL

kW

EER

IPLV

CAPACITY

(Btuh)

155

13

146,000

13.91

10.5

12.8

180

15

186,000

18.05

10.3

10.5

240

20

234,000

25.29

9.3

9.3

LEGEND

ARI

Air Conditioning and Refrigeration Institute

EER — Energy Efficiency Ratio
IPLV — Integrated Part-Load Values

NOTE:
Rated in accordance with ARI Standards 360-86.
Ratings are net values, reflecting the effects of circulating fan heat.
Ratings are based on:

Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature and 95 F db air entering out-
door unit.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db outdoor entering-air
temperature.