Configure the Adapter for Direct Connection

in RSLogix 5000 Software

What This Chapter Contains

In this example, a ControlLogix controller communicates with POINT I/O
modules via the 1734-AENT adapter using a direct connection.

The adapter makes a direct connection to each of the modules referenced by
the data. The modules presented in this chapter use RSLogix 5000 software,
version 11.

Set Up the Hardware

In this example, a ControlLogix chassis contains the Logix5555 processor in
slot 1 and a 1756-ENBT bridge module in slot 3.

Topic

Page

Set Up the Hardware

25

Create the Example Application

26

Configure the I/O

27

Add the Local EtherNet/IP Bridge to the I/O

Configuration

28

Add the POINT I/O Adapter to the I/O Configuration

30

Add the POINT I/O Modules to the I/O Configuration

33

Add the Relay Output Module

33

Add the Digital Output Module

36

Edit the Controller Tags

38

Create the Ladder Program

39

Download the Program to the Controller

39

Verify the Module Chassis Size

41

Configure the Adapter with Fixed IP Address

38

Recover From an Overloaded Adapter

44

ATTENTION

You must use series C POINT I/O modules with the 1734-AENT

adapter. Series A or B POINT I/O modules will not work with

this adapter.