Det-Tronics UD10 FlexVu Explosion-Proof Universal Display Unit User Manual

Page 13

Advertising
background image

11

95-8661

4.2

Sensor Connector

Power Supply Connector

Output Loop

Connector

MODBUS

Connector

R

ela

y Connect

or

P1

J2

J3

J4

P2

4-20 mA +

4-20 mA –

SHIELD

COM

RS485 A

RS485 B

HIGH ALARM COM

HIGH ALARM NC

HIGH ALARM NO

AUX ALARM COM

AUX ALARM NC

AUX ALARM NO

LOW ALARM COM

LOW ALARM NC

LOW ALARM NO

FAULT COM

FAULT NC

FAULT NO

24 VDC

24 VDC

+

SHIELD

24 VDC

24 VDC

+

SHIELD

SHIELD

C

ALIBR

A

TE

24 VDC

4-20 mA

24 VDC

+

P1-3

P1-2

P1-1

J2-3

J2-2

J2-1

J4-1

J4-2

J4-3

J4-4

J4-5

J4-6

J4-7

J4-8

J4-9

J4-10

J4-11

J4-12

J3-1

J3-2

J3-3

J3-4

J3-5

P2-6

P2-5

P2-4

P2-3

P2-2

P2-1

UD10

DISPLAY UNIT

E2440

24 VDC

INPUT

4-20 mA

PLC 4-20 mA INPUT CARD

+

250-600

OHMS

Notes: Resistor may be external if voltage input card is used.

Sinking resistance at PLC must be 250-600 ohms

for HART communication.

P12

Figure 10—UD10 Wired to PlC using 4-Wire Shielded Cable with 4-20 mA non-isolated Sourcing output

Figure 11—UD10 Wired to PlC with 4-20 mA isolated Sourcing output

Sensor Connector

Power Supply Connector

Output Loop

Connector

MODBUS

Connector

R

ela

y Connect

or

P1

J2

J3

J4

P2

4-20 mA +

4-20 mA –

SHIELD

COM

RS485 A

RS485 B

HIGH ALARM COM

HIGH ALARM NC

HIGH ALARM NO

AUX ALARM COM

AUX ALARM NC

AUX ALARM NO

LOW ALARM COM

LOW ALARM NC

LOW ALARM NO

FAULT COM

FAULT NC

FAULT NO

24 VDC

24 VDC

+

SHIELD

24 VDC

24 VDC

+

SHIELD

SHIELD

C

ALIBR

A

TE

24 VDC

4-20 mA

24 VDC

+

P1-3

P1-2

P1-1

J2-3

J2-2

J2-1

J4-1

J4-2

J4-3

J4-4

J4-5

J4-6

J4-7

J4-8

J4-9

J4-10

J4-11

J4-12

J3-1

J3-2

J3-3

J3-4

J3-5

P2-6

P2-5

P2-4

P2-3

P2-2

P2-1

UD10

DISPLAY UNIT

D2441

24 VDC

24 VDC

INPUT

4-20 mA

PLC 4-20 mA INPUT CARD

+

+

250-600

OHMS

Notes: Resistor may be external if voltage input card is used.

Sinking resistance at PLC must be 250-600 ohms

for HART communication.

P12

Important

Isolated operation is highly recommended to prevent noise or ripple on the main power source from interfering
with the HART function.