Det-Tronics UD10 FlexVu Explosion-Proof Universal Display Unit User Manual

Page 19

Advertising
background image

17

95-8661

4.2

Table 4—Troubleshooting Guide - Device Faults

Device Faults

Description

Recommended Action

loop Fault

Current loop below fault threshold

Check 4-20 mA loop wiring for shorts or opens.

Supply Voltage

Fault

24 volt power supply voltage too low

Verify proper wiring to the device and correct

voltage output from the power supply.

Calibration Fault

bad calibration

This fault can be caused if the calibration is

allowed to time out. if so, recalibrate.
Ensure that there is enough gas in the calibration

bottle to complete the calibration.
Ensure that the gas being used for calibration is

the correct type and concentration. it must match

the configured setting.

Memory Fault

Self-detected memory fault

Return to factory.

ADC Fault

Self-detected ADC fault

Return to factory.

internal Voltage

Fault

Self-detected voltage fault

Check supply voltage.
Return to factory.

Zero Drift

Sensor signal has drifted negative

Device may have been calibrated with background

gas present. Recalibrate the detector. Purge with

clean air if needed.

Temperature

Sensor Fault

Temperature sensor is out of range

Return to factory.

Wrong Sensor

Type

Wrong sensor type is installed

Sensor type must match configuration. Change

sensor or configuration.

lamp Fault

open or shorted lamp

Replace lamp.
Return to factory.

Alignment Fault

open path alignment problem

Align the device as specified in the instruction

manual.

blocked optic

Fault

optical path is blocked

locate and remove obstruction from the optical

path.

Cal line Active

Cal line is active at start-up

Ensure that the Cal line wiring is not shorted and

the switch is open.

low Cal line

Cal line is shorted.

Check wiring.

Sensor Fault

Self-detected fault with the sensor

Check sensor wiring.
Calibrate sensor.
Ensure that sensor type matches configuration.

noise Fault*

Excessive noise on signal

Check oPECl alignment.

Align ADC Fault*

Alignment ADC saturated

Check oPECl alignment.

Align Fault*

Alignment fault

Check oPECl alignment.

Align Warning*

Alignment warning

Check oPECl alignment.

DAC Fault

DAC fault detected

Return to factory.

General Fault

Unspecified fault

Verify correct power wiring and supply voltage.

Consult the factory.

High Fault

Detector output is higher than specified limit

Verify correct sensor type and calibration.

low Fault

Detector output is lower than specified limit

Verify correct sensor type and calibration.

Dirty optics

Detector optics are dirty

Perform the cleaning procedure as described in

the detector manual, then perform calibration.

Start Cal Fault

Calibration fault

Verify correct sensor type and calibrate.

*oPECl only.