Det-Tronics UD10 FlexVu Explosion-Proof Universal Display Unit User Manual

Page 4

Advertising
background image

2

95-8661

4.2

Table 1—Range and Default Values for Alarms and Calibration Gas Concentration

UD10 AlARM DATA

CAlibRATion

Gas Detector

High Alarm Value

low Alarm Value

Aux alarm Value

Cal Gas

GT3000--

Hydrogen Sulfide

Range

10-90%

5-50%

5-90%

30-90%

Default

40%

10%

40%

50%

GT3000--
Ammonia

Range

10-90%

5-50%

5-90%

30-90%

Default

40%

10%

40%

50%

GT3000--Chlorine

Range

10-90%

5-50%

5-90%

30-90%

Default

40%

10%

40%

50%

GT3000--
Hydrogen

Range

10-60%

5-50%

5-90%

30-90%

Default

40%

10%

40%

50%

GT3000--oxygen

Range

5-20.5% v/v

5-20.5% v/v

5-20.5% v/v

20.9% v/v

Default

18% v/v

18% v/v

18% v/v

20.9% v/v

GT3000--Carbon

Monoxide

Range

10-90%

5-50%

5-90%

30-90%

Default

40%

10%

40%

50%

GT3000--Sulfur

Dioxide

Range

10-90%

5-50%

5-90%

30-90%

Default

40%

10%

40%

50%

PiR9400

Range

10-60%

5-50%

5-90%

50%

Default

40%

10%

40%

50%

PiRECl

Range

10-60%

5-50%

5-90%

30-90%

Default

40%

10%

40%

50%

oPECl

Range

1-3 lFl-meters

0.25-3 lFl-meters

nA

nA

Default

2 lFl-meters

1 lFl-meter

nA

nA

C706x*

Range

10-90%

5-50%

5-90%

30-90%

Default

40%

10%

40%

50%

CGS

Combustible

Range

10-60%

5-50%

5-90%

50%

Default

40%

10%

40%

50%

Model 505/CGS

Combustible

Range

10-60%

5-50%

5-90%

n/A

Default

40%

10%

40%

n/A

nTMoS--

Hydrogen Sulfide

Range

10-90%

5-50%

5-90%

50%

Default

40%

10%

40%

50%

Generic Detector

Range

10-90%

5-50%

5-90%

n/A

Default

40%

10%

40%

50%

notes: All values are a percentage of full scale with the exception of oxygen, which is the actual percent of oxygen, and

oPECl, which is the value in lFl-meters.

low alarm must be less than or equal to the high alarm.

Changing the Measurement Range will reset all alarm and Cal Gas values to the default settings for the selected range.

Alarm relays are selectable for either normally energized or normally de-energized coils, with selectable latching or
non-latching contacts. Fault relay is normally energized (with no faults).

*Does not support C7064C hydrogen sulfide or C7065E oxygen, but includes C7064E hydrogen sulfide,
C7067E chlorine, C7066E carbon monoxide, and C7068E sulfur dioxide.