Det-Tronics UD10 FlexVu Explosion-Proof Universal Display Unit User Manual

Page 9

Advertising
background image

7

95-8661

4.2

WirinG

pOwER SUpply REQUIREmENTS
Calculate the total gas detection system power

consumption rate in watts from cold start-up. Select a

power supply with adequate capability for the calculated

load. Ensure that the selected power supply provides

regulated and filtered 24 Vdc output power for the entire

system. If a back-up power system is required, a float-type

battery charging system is recommended. If an existing

source of 24 Vdc power is being utilized, verify that system

requirements are met. The acceptable voltage range is

18-30 Vdc measured at the input to the UD10.

noTe

The power supply must meet the noise requirements
for HART systems. If noise or ripple on the main
power source could interfere with the HART
function, an isolated power source (Figure 11) is
recommended. (For detailed information regarding
power supply specifications, refer to the HART
Communication Foundation’s document “FSK
Physical Layer Specification” HCF_SPeC-54.)

wIRINg CABlE REQUIREmENTS
Always use proper cabling type and diameter for input

power as well as output signal wiring. 14 to 18 AWG

shielded stranded copper wire is recommended. Correct

wire size depends on the device and wire length. Refer

to the appropriate Appendix for additional information.

The maximum cable length from power source to UD10 is

2000 feet. Maximum cable length from UD10 to sensor

is 2000 feet.

noTe

The use of shielded cable in conduit or shielded
armored cable is highly recommended. In
applications where the wiring is installed in
conduit, dedicated conduit is recommended.
Avoid low frequency, high voltage, and
non-signaling conductors to prevent nuisance
eMI problems.

CautIon

The use of proper conduit installation techniques,
breathers, glands, and seals is required to prevent
water ingress and/or maintain the explosion-proof
rating.

SHIElD CONNECTIONS
The UD10 provides terminals for proper grounding of

wiring cable shields (located on the sensor, 4-20 mA,

and operating power terminal blocks). These shield

terminals are not connected internally, but are connected

to ground through capacitors. The capacitors ensure an

RF ground, while preventing 50/60 Hz ground loops.

Ground all shields as shown in the wiring examples

throughout this manual.

Important

For proper grounding, all junction boxes / metal
enclosures must be connected to earth ground.

The following are required for installations requiring CE

Mark compliance:
• For shielded cable installed in conduit, attach the wire

shields to the “shield” connections on the terminal

blocks, or to earth ground on the case.

• For installations without conduit, use double shielded

cable. Terminate the outer shield to earth ground on

the case. Terminate the inner shield to the “shield”

connection on the terminal blocks.

JUmpER SETTINg FOR 4-20 mA lOOp
In order for the 4-20 mA current loop to operate properly,

+24 Vdc must be applied to terminal P1-3. This can be

accomplished in one of two ways:
• For a non-isolated 4-20 mA loop, set jumper plug as

shown in Figure 4. This applies +24 Vdc to P1-3 via an

internal connection to terminals P2-2 and P2-5.

• If the 4-20 mA loop will receive power from a source

other than the UD10’s main power source (isolated),

set the jumper plug as shown in Figure 5 to remove

the internal connection.

FOUNDATION FIElDBUS (Optional)
Some UD10 models allow the use of either RS485/

MODBUS or Foundation Fieldbus communication via

connection to J2 on the terminal board. Four jumpers

are provided to select between the two protocols. If the

device is equipped for Foundation Fieldbus, it will be

shipped from the factory with the jumpers preset for that

mode. If the user wants to switch to RS485/MODBUS

(for example, to retrieve logs), the four jumpers can

easily be moved. Figures 6 and 7 show the jumper

settings for each mode of communication.

Note that the pin identification for the J2 connector

is different for each communication protocol. For

Foundation Fieldbus it is “– +”. For RS485/MODBUS

it is “B A com”.

Advertising