chAnGinG operAtinG moDes

When used with a PIR9400, the operating mode of

the UD10 must be changed from “HART Device” to

“PIR9400” mode. Refer to the “Startup” section of this

manual for details.

cAlibrAtion

To initiate calibration of the PIR9400 from the UD10

Display:

1. Using the magnet to activate the switches on the

UD10 display, navigate to the “Calibration” menu.

Main Menu
Process Vars
Display Status
Device Status
Display Setup
Device Setup
Device Cal
Display Test
Device Test

Device Cal

Calibration

Calibration

Execute
Abort

2. Activate “Execute” (Enter/Select) to start calibration.

3. The UD10 will display “Waiting for Zero” on the main

display screen.

4. The UD10 will then display “Waiting for Gas” on the

screen.

5. Apply calibration gas to the PIR9400.

6. The UD10 will continue to display “Waiting for Gas”

on the screen.

7. When the UD10 displays “Remove Cal Gas” on

the screen, remove the calibration gas from the

PIR9400.

8. The UD10 automatically returns to the normal mode

after successful calibration.

To initiate calibration from the PIRTB Termination Box

while monitoring calibration using the UD10 display:

1. Using the magnet, activate the magnetic calibration

switch on the PIRTB Termination Box. The LED at

the PIRTB turns from off to steady red.

2. The UD10 will display “Waiting for Zero” on the main

display screen, with a steady red LED at the PIRTB.

3. The UD10 will then display “Waiting for Gas” on the

screen, while the LED at the PIRTB is flashing red.

4. Apply calibration gas to the PIR9400 detector.

5. The UD10 will display “Waiting for Span” on the

screen, with a red flashing LED at the PIRTB.

6. When the UD10 displays “Remove Cal Gas” on the

screen and the LED at the PIRTB turns off, remove

the calibration gas.

7. After successful calibration, the UD10 automatically

returns to the normal mode, and the LED on the

PIRTB remains off.

UD10 mA Output During Calibration

(UD10 with pIR9400)

UD10 Display Reading

Standard

mode

Replicate

mode

Waiting for Zero

3.8

2.2

Waiting for Gas

3.8

3.8

Waiting for Span

3.8

3.8

Remove Cal Gas

3.8

3.8

back to normal

4.0

4.0

CALIBRATE SWITCH

B2056

HOLD CALIBRATION MAGNET

AT OUTSIDE BASE OF JUNCTION

BOX AT THIS LOCATION

TO ACTIVATE CALIBRATION SWITCH

REMOTE LED

PiRTb Termination box