G-2

95-8661

4.2

UD10 Wired to GT3000 Detector with Sensor Termination box

NOTE 1

GROUND THE SHIELD AT THE DISPLAY

UNIT END ONLY.

NOTE 2

HOUSINGS MUST BE ELECTRICALLY

CONNECTED TO EARTH GROUND.

SEE NOTE 1

UD10 DISPLAY UNIT

C2401

RED

BLACK

GT3000

GAS DETECTOR

SENSOR TERMINATION BOX

Sensor Connector

Power Supply Connector

Output Loop

Connector

MODBUS

Connector

R

ela

y Connect

or

P1

J2

J3

J4

P2

4-20 mA +

4-20 mA –

SHIELD

COM

RS485 A

RS485 B

HIGH ALARM COM

HIGH ALARM NC

HIGH ALARM NO

AUX ALARM COM

AUX ALARM NC

AUX ALARM NO

LOW ALARM COM

LOW ALARM NC

LOW ALARM NO

FAULT COM

FAULT NC

FAULT NO

24 VDC

24 VDC

+

SHIELD

24 VDC

24 VDC

+

SHIELD

SHIELD

C

ALIBR

A

TE

24 VDC

4-20 mA

24 VDC

+

P1-3

P1-2

P1-1

J2-3

J2-2

J2-1

J4-1

J4-2

J4-3

J4-4

J4-5

J4-6

J4-7

J4-8

J4-9

J4-10

J4-11

J4-12

J3-1

J3-2

J3-3

J3-4

J3-5

P2-6

P2-5

P2-4

P2-3

P2-2

P2-1

RED

RED

BLA

CK

BLACK

GREEN

orientAtion

The device must be mounted in a vertical position only,

with the GT3000 pointing down.

liVe mAintenAnce

noTe

The sensor module on the GT3000 Gas Detector
can be hot swapped, i.e. replaced without
removing power or de-classifying the area. To
replace a GTX Transmitter connected to the UD10
with a new transmitter or a different detector type,
the area

must be de-classified.

noTe

Removing the sensor module with power applied
will result in a fault condition until a new sensor
module of the same type is installed. When
replacing an oxygen sensor, this action will also
result in an alarm condition as the decreasing
4-20 mA signal passes through the alarm range.
Inhibit response devices to prevent unwanted
actuation.

For complete information regarding sensor replacement

with the GT3000 Gas Detector, refer to the GT3000

instruction manual number 95-8616.