Appendix g, Wiring – Det-Tronics UD10 FlexVu Explosion-Proof Universal Display Unit User Manual

Page 33

Advertising
background image

G-1

95-8661

4.2

AppenDix G

UD10 with gT3000 TOxIC gAS DETECTOR

noTe

For complete information regarding the GT3000 Gas Detector, refer to instruction manual 95-8616.

WirinG

4000

3500

3000

2500

2000

1500

1000

500

0

18

19

20

21

22

23

24

25

26

27

28

29

30

Power Supply Voltage

Dist

ance in f

t.

UD10 with GT3000

12
14
16
18

AWG

Wire Size

Notes: Maximum cable length from power source to UD10 is 2000 feet.

Maximum cable length from UD10 to sensor/STB termination box is 2000 feet.

Sensor Connector

Power Supply Connector

Output Loop

Connector

MODBUS

Connector

R

ela

y Connect

or

P1

J2

J3

J4

P2

4-20 mA +

4-20 mA –

SHIELD

COM

RS485 A

RS485 B

HIGH ALARM COM

HIGH ALARM NC

HIGH ALARM NO

AUX ALARM COM

AUX ALARM NC

AUX ALARM NO

LOW ALARM COM

LOW ALARM NC

LOW ALARM NO

FAULT COM

FAULT NC

FAULT NO

24 VDC

24 VDC

+

SHIELD

24 VDC

24 VDC

+

SHIELD

SHIELD

C

ALIBR

A

TE

24 VDC

4-20 mA

24 VDC

+

P1-3

P1-2

P1-1

J2-3

J2-2

J2-1

J4-1

J4-2

J4-3

J4-4

J4-5

J4-6

J4-7

J4-8

J4-9

J4-10

J4-11

J4-12

J3-1

J3-2

J3-3

J3-4

J3-5

P2-6

P2-5

P2-4

P2-3

P2-2

P2-1

GT3000

GAS DETECTOR

BLACK

RED

GREEN

SEE NOTE 1

NOTE 1

CONNECT THE GREEN SENSOR LEAD

TO THE CHASSIS GROUND LUG ON THE

INSIDE BOTTOM OF THE DISPLAY ENCLOSURE.

NOTE 2

UD10 HOUSING MUST BE ELECTRICALLY

CONNECTED TO EARTH GROUND.

UD10

DISPLAY UNIT

C2400

GT3000 Detector Wired Directly to UD10