Det-Tronics X2200 UV Flame Detector with Pulse Output User Manual

Page 10

Advertising
background image

95-8552

5.3

8

Figures 11 and 12 provide examples of typical

installations with an X2200 wired to a fire alarm

panel.

Figure 13 shows an EOL resistor installed within the

integral wiring compartment of the detector (refer to

“EOL Resistors” for details).

2. Check all field wiring to be sure that the proper

connections have been made.

Important

Do not test any wiring connected to the detector
with a meg-ohmmeter. Disconnect wiring at
the detector before checking system wiring for
continuity.

3. Make the final sighting adjustments and ensure that

the mounting bracket hardware is tight.

Figure 3—Q9033 Mounting Bracket Dimensions in Inches (cm)

(Refer to Figure 1 for Correct Detector Orientation)

9

8

7

6

5

4

3

2

1

19

18

17

16

15

14

13

12

11

PULSE OUT

COM FIRE

N.O. FIRE

N.C. FIRE

COM FAULT

N.O. FAULT

24 VDC +

24 VDC –

24 VDC –

29

28

27

26

25

24

23

22

21

SPARE

SPARE

RS-485 A

RS-485 B

MAN

Oi

A2070

Figure 5—X2200 Wiring Terminal Identification

Figure 4—X2200 Terminal Block

13.1

(33.4)

10.6

(27.0)

4.0

(10.2)

4.0

(10.2)

3.0

(7.6)

3.0

(7.6)

4X ø0.42

(1.1)

E2069

NOTE: THIS ILLUSTRATION SHOWS THE
DETECTOR MOUNTED AT THE 10° MINIMUM.
THESE DIMENSIONS WILL CHANGE BASED
ON THE DETECTOR’S MOUNTING ANGLE.