19

95-8552

5.3

ENCLOSURE MATERIAL—

Copper-free aluminum (painted) or 316 stainless steel.

VIBRATION—

Conformance per FM 3260: 2000, MIL-STD 810C (Curve AW),

DIMENSIONS—

See Figure 16.

WIRING—

Field wiring screw terminals are UL/CSA rated for

up to 14 AWG wire, and are DIN/VDE rated for 2.5

mm2 wire. Screw terminal required torque range is

3.5–4.4 in.-lbs. (0.4-0.5 N·m).

14 AWG (2.08 mm2) or 16 AWG (1.31 mm2) shielded

cable is recommended.

Important:

18 Vdc minimum must be available at the

detector. For ambient temperatures below –10°C and

above +60°C use field wiring suitable for both minimum

and maximum ambient temperature.

THREAD SIZE—

Conduit connection: Four entries, 3/4 inch NPT or M25.

Conduit seal not required.

SHIPPING WEIGHT (Approximate)—

Aluminum:

6 pounds (2.75 kilograms).

Stainless Steel: 10 pounds (4.5 kilograms).

Swivel Mount (AL): 6 pounds (2.75 kilograms).

Swivel Mount (SS): 14 pounds (6.4 kilograms).

WARRANTY PERIOD—
3 years.

CERTIFICATION—

FM

APPROVED

®

For complete FM certification details, refer to Appendix A.
For complete CSA certification details, refer to Appendix B.

FM

APPROVED

®

For complete ATEX/CE certification details, refer to Appendix C.

NOTE

Operational performance verified from -40°C to +75°C.

NOTE

An optional third party addressable module can
only be used within the Ex d flameproof model
unless the addressable module is component
certified as Ex e for use within the Ex d e
increased safety model.

NOTE

Refer to “EOl Resistors” section for installation
details. All cable entry devices and blanking
elements shall be certified to “E-generation” or
“ATEX” standards, in type of explosion protection
increased safety “e” or flameproof enclosure “d” (as
applicable), suitable for the conditions of use and
correctly installed. They shall maintain the degree
of ingress protection IP66 for the apparatus.
Unused apertures shall be closed with suitable
blanking elements.

NOTE

For ATEX installations, the X2200 detector housing
must be electrically connected to earth ground.

For complete IECEx certification details, refer to Appendix D.

vdS

Performance per EN54-10,

Certificate of Approval G-203083.

EC-Certificate of Conformity

08 0786 – CPD – 20777

EN54-10 Flame detectors - Point detectors.

For complete VdS certification details, refer to Appendix E.

10.2

(25.9)

4.8

(12.2)

4.7

(11.9)

B2223

Figure 16—Dimensions in Inches (cm)