Det-Tronics X2200 UV Flame Detector with Pulse Output User Manual

Page 9

Advertising
background image

7

95-8552

5.3

pROTECTION AGAINST MOISTURE DAMAGE
It is important to take proper precautions during installation

to ensure that moisture will not come in contact with

the electrical connections of the system. The integrity

of the system regarding moisture protection must be

maintained for proper operation and is the responsibility

of the installer.

If conduit is used, we recommend installing drains,

according to local codes, at water collection points

to automatically drain accumulated moisture. It is

also recommended to install at least one breather,

according to local codes, at upper locations to provide

ventilation and allow water vapor to escape.

Conduit raceways should be inclined so that water will

flow to low points for drainage and will not collect inside

enclosures or on conduit seals. If this is not possible,

install conduit drains above the seals to prevent the

collection of water or install a drain loop below the

detector with a conduit drain at the lowest point of the

loop.

Conduit seals are not required for compliance with

explosion-proof installation requirements, but are highly

recommended to prevent water ingress in outdoor

applications. Units with M25 thread must use an IP66

washer or an O-ring sealed adapter/gland to prevent

water ingress.

wIRING pROCEDURE
wire Size and Type
The system should be wired according to local codes.

The wire size selected should be based on the number

of detectors connected, the supply voltage and the

cable length. Typically 14 AWG (2.08 mm

2

) or 16 AWG

(1.31 mm

2

) shielded cable is recommended. Wires

should be stripped 3/8 inch (9 mm). In some cases

where the X2200 is replacing existing pulse output

detectors, the wiring and power supplies may not be

adequate. Consult the factory for assistance.

NOTE

A minimum input voltage of 18 Vdc must be
present at the X2200.

The use of shielded cable is required to protect against

interference caused by EMI and RFI. When using cables

with shields, terminate the shields as shown in Figures

6 through 10. Consult the factory if not using shielded

cable.

The “B” (pulse output) and “D” (oi driver) leads from

each detector should be shielded from the “B” and

“D” leads of all other detectors in order to prevent

false alarms resulting from crosstalk between zones.

It is recommended that the “A” and “C” leads also be

shielded to provide maximum immunity to EMI/RFI.

(See Figures 6 to 10.)

In applications where the wiring cable is installed in

conduit, the conduit must not be used for wiring to other

electrical equipment.

If disconnection of power is required, separate

disconnect capability must be provided.

CaUtIon

Installation of the detector and wiring should be
performed only by qualified personnel.

Detector Mounting
Install the swivel mounting bracket assembly on the wall.

The installation surface should be free of vibration and

suitable to receive 1/4 inch (M6) screws with a length of

at least 1 inch (25 mm), and have sufficient capacity to

hold the detector and bracket weight. Refer to Figure 3

for dimensions.

Detector wiring

Important

If installing an X2200 in place of an existing
detector, be sure to move the “A” lead (detector
power) at the controller from the +290 Vdc source
to the +24 Vdc source.

Do not apply 290 Vdc to

the X2200.

1. Make field connections following local ordinances

and guidelines in this manual.

Figure 4 shows the wiring terminal strip located

inside the detector’s integral junction box.

Figure 5 shows the wiring terminal identification

for the X2200 detector with pulse output.

Leave the shield open at the detector end and

permanently isolate it from accidental contact

with the case and/or other conductors. At the

controller/fire panel end, connect the shield

and power minus (–) to chassis (earth) ground

either directly or through a 0.47 µF 400 Volt

non-polarized capacitor (not supplied). (Refer

to Figures 6 through 10.)

Advertising