95-8552

5.3

28

aPPENDIX C

ATEX / CE Approval

EC-TYpE EXAMINATION CERTIFICATE

DEMKO 02 ATEX 132195X
Increased Safety Model

Flameproof Model

0539

FM

APPROVED

®

II 2 G

0539

FM

APPROVED

®

II 2 G

Ex d e IIC T5–T6 Gb

Ex d IIC T5–T6 Gb

T6 (T

amb

–50°C to +60°C)

T6 (T

amb

–55°C to +60°C)

T5 (T

amb

–50°C to +75°C)

T5 (T

amb

–55°C to +75°C)

IP66.

IP66.

Compliance with:
EN 60079-0: 2009

EN 60079-1: 2007

EN 60079-7: 2007

EN / IEC 60529: 2001.

INSTALLATION INSTRUCTIONS
The field wiring connections in the terminal compartment are ATEX certified and accepts wiring diameter from 14 AWG

(2.08 mm

2

) to 22 AWG (0.33 mm

2

).

The flame detector model X2200UV shall be installed according to the instructions given by the manufacturer.

The cable entry devices shall be certified in type of explosion protection flameproof enclosure “d” for use with the

terminal compartment in type of explosion protection flameproof enclosure “d”, or in type of explosion protection

increased safety “e” for use with the terminal compartment in type of explosion protection increased safety “e”. They

shall be IP66 rated, suitable for the conditions of use and correctly installed.

Unused entries shall be closed with suitable certified blanking elements.

The metal housing for the Ultraviolet (UV) flame detector type X2200 must be electrically connected to earth ground.

For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum

ambient temperature.

Special conditions for safe use:
The EOL resistor can only be used within the flameproof terminal compartment.

EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed

2.5 watts.

The Ultraviolet (UV) flame detector type X2200 is to be installed in places where there is a low risk of mechanical

damage.