95-8552

5.3

26

FM Approval and performance Report – Continued

X2200M FIELD OF vIEw

high Sensitivity (Standard Mode)

Fuel

Size

Distance

feet (m)

horizontal

(degrees)

Typical

Response Time

(seconds)

vertical

(degrees)

Typical

Response
(seconds)

Black Powder

40 grams

5

(1.5)

+45

–45

0.1
0.1

+45

–30

0.1
0.1