Det-Tronics X2200 UV Flame Detector with Pulse Output User Manual

Page 4

Advertising
background image

95-8552

5.3

2

OUTpUTS
Relays
The detector is furnished with fire and fault relays. The

relays are rated 5 amperes at 30 Vdc.

The Fire Alarm relay has redundant terminals and normally

open / normally closed contacts, normally de-energized

operation, and latching or non-latching operation.

The Fault relay has redundant terminals and normally

open contacts, normally energized operation, and

latching or non-latching operation.

Latching relays can be reset by removing input power

(0.1 second minimum).

An alarm condition will normally over-ride a fault condition,

unless the nature of the fault condition impairs the ability

of the detector to generate or maintain an alarm output,

i.e. loss of operating power.

LED
A tricolor LED on the detector faceplate indicates

normal condition and notifies personnel of fire alarm or

fault conditions. Table 1 indicates the condition of the

LED for each detector status.

OpTICAL INTEGRITY (

oi

)

Automatic

oi

The X2200 includes the Automatic Optical Integrity

(oi) feature — a calibrated performance test that is

automatically performed once per minute to verify

complete detector operation capabilities. No testing

with an external test lamp is required. The detector

automatically performs the same test that a maintenance

person with a test lamp would perform — once every

minute. However, a successful automatic oi test does

not produce an alarm condition.

The X2200 signals a fault condition when less than half

of the detection range remains. This is indicated by the

fault relay and is evident by the yellow color of the LED

on the face of the detector. See the “Troubleshooting”

section for further information.

Magnetic

oi / Manual oi

CaUtIon

These tests require disabling of all extinguishing
devices to avoid release resulting from a
successful test.

The detector incorporates both magnetic oi and

manual oi test capabilities. These tests provide pulses

(80 to 100 CPS) to the controller (R7404 or R7494)

when the detector is not in fault. If the test is successful,

the controller indicates a fire and the appropriate zone

output is active.

NOTE

If the detector is in a fault condition, a successful
magnetic

oi

or manual

oi

test cannot be

performed.

The magnetic oi test is initiated by placing a magnet

at the marked location (mag oi) on the outside of

the detector. This action causes the detector to

immediately send pulses to the controller. Controller

response is as follows:

• The Zone LED blinks.
• The digital display indicates which Zone is in alarm.
• The status indicator shows “6” (fire).

Table 1—Detector Status Indicator

Detector Status

LED Indicator

Power On/Normal Auto

oi

(no fault or fire alarm)

Green

Power On/Normal Man

oi

Green, flashing on for 0.5 sec.

every 5 sec.

Fault

Yellow

Pre-Alarm/Background UV

Red, flashing on for 500 ms.

and off for 500 ms.

Fire (Alarm)

Steady Red

On Power-Up, The LED Flashes in Sequence as Follows,

Indicating Sensitivity and Signal Processing Status

Low UV Sensitivity
Medium UV Sensitivity
High UV Sensitivity
Very High UV Sensitivity

One Red Flash

Two Red Flashes

Three Red Flashes

Four Red Flashes

Stand. UV Signal Process.
Arc Rej. UV Signal Process.

One Yellow Flash

Two Yellow Flashes

Advertising