Maintenance – Det-Tronics X2200 UV Flame Detector with Pulse Output User Manual

Page 19

Advertising
background image

17

95-8552

5.3

maINTENaNCE

Important

Periodic flamepath inspections are not
recommended, since the product is not intended
to be serviced and provides proper ingress
protection to eliminate potential deterioration of the
flamepaths.

WarnIng

The sensor module (“front” half of the detector)
contains no user serviceable components
and should never be opened. The terminal
compartment is the only part of the enclosure that
should be opened by the user in the field.

To maintain maximum sensitivity and false alarm

resistance, the viewing windows of the X2200 must be

kept relatively clean. Refer to the procedure below for

cleaning instructions.

CLEANING pROCEDURE

CaUtIon

Disable any extinguishing equipment that is
connected to the unit to prevent unwanted
actuation.

To clean the windows and oi plate, use Det-Tronics

window cleaner (part number 001680-001) and a soft

cloth, cotton swab or tissue and refer to the procedure

below.

1. Disable any extinguishing equipment that is

connected to the unit.

NOTE

Remove input power when cleaning the detector
windows. The rubbing motion on the surface of
the windows during cleaning can create static
electricity that could result in unwanted output
activation.

2. To clean the optical surfaces, remove the oi plate

following the procedure described below.

3. Thoroughly clean the viewing window and reflective

surfaces of the oi plate using a clean cloth, cotton

swab or tissue, and Det-Tronics window cleaning

solution. If a stronger solution is needed, isopropyl

alcohol may be used.

4. Re-install the oi plate following the procedure

described below.

oi

pLATE REMOvAL

1. Disable any extinguishing equipment that is

connected to the unit.

2. Loosen the two captive screws, then grasp the oi

plate by the visor and remove it from the detector.

See Figure 14.

3. Thoroughly clean the oi plate reflective surfaces,

holding it by its edges to avoid leaving fingerprints

on the inside reflective surface.

4. Re-install the oi plate. Ensure that the plate is flat

on the detector surface. Tighten the oi plate screws

securely (40 oz/inches).

NOTE

If the

oi

plate is removed, be sure to install

the original

oi

plate.

oi

plates are not

interchangeable and should not be mixed with

oi

plates from other detectors. If corrosive

contaminants in the atmosphere cause the

oi

plate surface to deteriorate to the extent that it
is no longer possible to restore it to its original
condition, it must be replaced. Consult factory for

oi

plate replacement procedure.

pERIODIC ChECKOUT pROCEDURE
A checkout of the system using the manual or magnetic

oi feature should be performed on a regularly scheduled

basis to ensure that the system is operating properly. To

test the system, perform the “Manual oi Test,” “Count Test

Mode” or “Fire Alarm Test” as described in the “Startup

Procedure” section of this manual.

CLOCK BATTERY
The real time clock has a backup battery that will operate

the clock with no external power for nominally 10 years.

It is recommended that the battery be replaced every

7 years. Return the device to the factory for battery

replacement.

NOTE

If the backup battery is depleted, there is no effect
on the operation of the flame detector, but the time
stamping of the data log may be affected.

LOOSEN TWO

CAPTIVE SCREWS

GRASP VISOR AND

REMOVE

oi PLATE

B2135

Figure 14—

oi

Plate Removal