Det-Tronics X2200 UV Flame Detector with Pulse Output User Manual

Page 27

Advertising
background image

25

95-8552

5.3

FM Approval and performance Report – Continued

X2200M RESpONSE ChARACTERISTICS

high Sensitivity

X2200M RESpONSE ChARACTERISTICS IN ThE pRESENCE OF FALSE ALARMS

high Sensitivity (Standard Mode)

X2200M FALSE ALARM IMMUNITY

MODEL X2200M
The X2200M uses a sensor that has a broader spectrum than the standard sensor. It is designed to detect fires with

unusual chemistry such as black powder. Consult factory for usage recommendations.

Fuel

Size

Distance

feet (m)

Typical Response Time

(seconds)

Mode

Black Powder

40 grams

10 (3)

0.1

Standard

False Alarm Source

Distance

feet (m)

Fire Source

Distance

feet (m)

Typical

Response Time

(seconds)

Sunlight, direct, reflected, modulated & unmodulated

2-inch dia n-Heptane

10 (3)

<15

70 w sodium vapor lamp, modulated & unmodulated

3 (0.9)

1 x 1 foot n-Heptane

40 (12)

0.1

250 w vapor lamp, modulated & unmodulated

3 (0.9)

1 x 1 foot n-Heptane

40 (12)

0.1

300 w incandescent lamp, modulated & unmodulated

3 (0.9)

1 x 1 foot n-Heptane

40 (12)

0.1

500 w halogen lamp, modulated & unmodulated

3 (0.9)

1 x 1 foot n-Heptane

40 (12)

0.1

1500 w electric radiant heater, modulated & unmodulated

10 (3)

1 x 1 foot n-Heptane

40 (12)

0.1

2-34 w fluorescent lamps, modulated & unmodulated

3 (0.9)

1 x 1 foot n-Heptane

40 (12)

0.1

False Alarm Source

Distance

feet (m)

Modulated Response

Unmodulated Response

Sunlight, direct, reflected

No Alarm

No Alarm

70 w sodium vapor lamp

3 (0.9)

No Alarm

No Alarm

250 w vapor lamp

3 (0.9)

No Alarm

No Alarm

300 w incandescent lamp

3 (0.9)

No Alarm

No Alarm

500 w halogen lamp

3 (0.9)

No Alarm

No Alarm

1500 w electric radiant heater

3 (0.9)

No Alarm

No Alarm

2-34 w fluorescent lamps

3 (0.9)

No Alarm

No Alarm

Advertising