Warning – Elkhart Brass Sidewinder 7100 EXM Monitor User Manual

Page 24

Advertising
background image

24

F. Stow Position
The Stow Position is a preset position that can be used to bring the monitor into a position suitable for

when the system is powered off. A stow position must be within the allowed travel area defined by any

travel limits or keep-out zones, therefore it is recommended that travel limits and keep-out zones are

set before setting a stow position.

Move the monitor to the desired position while in normal operation; not in setup mode. If a travel

limit or keep-out zone boundary is met, move the discharge off the boundary a short distance.

Put the EXM system into Setup Mode (reference Part B of the Operating Instructions section)

Press the FOG and OSCILLATE buttons at the same time (rotate thumbwheel down for FOG on

Joystick)

This position will be the Stow Position when the system is brought out of Setup Mode

Simply press and hold the FOG and OSCILLATE buttons for three seconds to put the monitor into

the Stow Position while outside of Setup Mode (rotate thumbwheel down for FOG on Joystick)

Warning!

Water SHOULD NOT be flowing while stowing the monitor.

G. Motor Speed
The speed of both the horizontal and vertical motors can be changed from something different than

that set during configuration of the EXM system. The monitor’s horizontal and vertical motors can be

set to either Fast or Slow in one of four combinations.

Put the EXM system into the Setup Mode (reference Part B of the Operating Instructions section)

Press the OSCILLATE button to cycle through the various motor speed combinations

o

The horizontal, vertical, and nozzle LED’s on the monitor are used to show which motor

speed combination the monitor will be set at after Setup Mode is exited

o

All Yellow LED’s “OFF” places both motors in fast mode

o

One Yellow LED only “ON” indicates horizontal motor fast and vertical motor slow mode

o

Two Yellow LED’s only “ON” indicates horizontal motor slow and vertical motor fast mode

o

Three Yellow LED’s “ON” places both motors in slow mode

When the system is brought out of Setup Mode, the motor speeds will be changed to the

combination selected

H. Clear All Function
The Clear All Function allows the user to remove any Travel Limits, Keep-Out Zones, or Stow Positions

set while in Setup Mode. When the Clear All Function is used, it will remove all of the previously listed

operations. The Clear All Function will not affect calibration points, Motor Speed, or Preset valve

positions.

Put the EXM system into Setup Mode (reference Part B of the Operating Instructions section)

Press the OPEN and CLOSE buttons simultaneously

All set Travel Limits, Keep-Out Zones, and Stow Positions will be removed from the system

Advertising