Monitor Position Feedback Message
Repetition rate:

100mS

Data Length:

8

Extended Data Page: 0

Data Page:

0

PDU Format:

255

PDU Specific:

240

Default Priority:

6

Parameter Group Number: 255,240 (0x00FFF0) – broadcast message

Start Position Length

Parameter

0

1 byte

0xFD – Command

1

2 bytes

Horizontal Position Feedback (0000-3600)

0000 corresponds to the left most allowable operating position.

1/10 degree resolution

High byte is byte 1, Low byte is byte 2

3

2 bytes

Vertical Position Feedback (0000-3600)

0000 corresponds to straight up when monitor is mounted vertically.

1/10 degree resolution

High byte is byte 3, Low byte is byte 4

5.0

1 bit

1 for at left keep out area, 0 for not at left keep out area

5.1

1 bit

1 for at right keep out area, 0 for not at right keep out area

5.2

1 bit

1 for at left programmed limit, 0 for not at left programmed limit

5.3

1 bit

1 for at right programmed limit, 0 for not at right programmed limit

5.4

1 bit

1 at top limit, 0 for not at top limit

5.5

1 bit

1 for bottom limit, 0 for not at bottom limit

5.6

1 bit

1 for in Extended Travel region, 0 for not in Extended Travel region

5.7

1 bit

1 for Extended Travel enabled, 0 for Extended Travel disabled

6.1

1 bit

Power/CAN cable pin 3 state (0 = grounded, 1 = not grounded)

6.2

1 bit

Power/CAN cable pin 4 state (0 = grounded, 1 = not grounded)

6.3-6.7

6 bits

Reserved

7

1 byte

Reserved