Main power – ElmoMC Gold Line Digital Servo Drives-Gold Duo User Manual

Page 26

Advertising
background image

Gold Duo Installation Guide

MAN-G-DUOIG-E (Ver. 1.500)

||Main and Auxiliary Power|

www.elmomc.com

26

Table of Contents

6.3.2.

Main Power

Pin

Signal

Function

Cable (Wires)

J13/1

VP+

Pos. Power input

DC Power

J13/2

VP+

Pos. Power input

DC Power

J13/3

PR

Power return

DC Power

J13/4

PR

Power return

DC Power

J13/5

PE

Protective earth

DC Power

5-Pin Phoenix 5 mm Pitch ‘HC’

5-Pin Phoenix Plug-in

Connector

Table 5: Main Power Pin Assignments

Connect the DC power cable to the VP+ and PR terminals on the Main Power Connector.

To connect the DC power supply:
1.

The source of the 12 to 195 VDC power supply must be isolated.

2.

For best immunity, it is highly recommended to use twisted and shielded cables for the DC
power supply. A 3-wire shielded cable should be used. The gauge is determined by the
actual current consumption of the motor.

3.

Connect the cable shield to the closest ground connection near the power supply.

4.

Connect the PE to the closest ground connection near the power supply.

5.

Connect the PR to the closest ground connection near the power supply.

6.

Before applying power, first verify the polarity of the connection.

Advertising